Bosch FCS-320-TM Series Conventional Aspirating Smoke Detectors: Commissioning

Commissioning: Bosch FCS-320-TM Series Conventional Aspirating Smoke Detectors

background image

FCS-320-TM | FCS-320-TM-R

en

21

Bosch Sicherheitssysteme GmbH

F.01U.123.590 | 1.0 | 2009.11

also be activated; otherwise, the fire location cannot be identified.

The "Main alarm after ROOM·IDENT" function is deactivated as standard.

Commissioning

1.

Insert the FCS-320-TM detection device into the pre-mounted housing base, which has 

been checked for correct wiring.

2.

Replug the X4 jumper when inserting the detection device (PIN 1-2 or PIN 2-3, or vice 

versa). Replugging will cause airflow calibration to be carried out automatically (see 

Figure 4

Page 4

).

3.

The green operation display flashes when the FCS-320-TM is initializing. If initialization is 

complete, the operation display lights up permanently.

4.

The airflow of the FCS-320-TM must not be affected during the initialization phase.

Fire Source Identification Commissioning

Fire source identification is set using the FAS-ASD-DIAG Diagnostic Software via the 

"ROOM·IDENT" screen.

1.

Click the [Train] button. This opens the view with adjustable values used to determine 

the transport times for fire source identification in areas A-E.

2.

First enter the number of air sampling openings.

3.

Then enter the blowing out time and voltage of the blowing out and aspiration fan.

You can access the Help function by clicking the question mark to the right of the 

relevant setting.

4.

Click the appropriate aspiration point (A-E) for which the transport time is to be 

determined.

5.

Enter the preselection time necessary to reach the aspiration point and supply the 

smoke. Once the selected preselection time has expired, the appropriate smoke 

aspiration point must be charged with smoke. Once the preselection time has expired, 

the smoke must be available at the aspiration point for another 10 to 15 seconds.

6.

Using the smoke level, check that there is no smoke in the aspiration pipe.

7.

Click the [Start] button. The FCS-320-TM-R switches to the aspiration pipe blowing out. 

The display of the aspiration point concerned is yellow.

8.

Once the preselection time has expired, switch the FCS-320-TM-R to aspiration. The 

smoke must now be available at the selected aspiration point. The smoke level will be 

displayed if smoke is detected by the FCS-320-TM-R. The display of the selected 

aspiration point turns green and the determined time is entered. Teaching mode for the 

selected aspiration point is exited.

NOTICE! 

The following FCS-320-TM designation refers to all FCS-320-TM series (FCS-320-TM, 

FCS-320-TM-R) versions. Specific references are made to differences between the individual 

versions.