Figure 5 12 V mode variants

The 12 V mode can be configured using one or two

rechargeable batteries. For a one-battery installation, refer to

Figure 5 - on the left, and perform the following procedure:

1. Connect B1 to the power supply position labbeled BAT.

2. Connect B2a (black) to the rechargeable battery’s -

terminal, and B2b (red) to the rechargeable battery’s +

terminal.

3. Connectors B3a and B3b remain unused - fix them with the

bracket J.

For the two-battery installation, refer to Figure 5 - on the right,

and perform the following procedure:

1. Connect B1 to the power supply position labbeled BAT.

2. Connect B2a (black) to the rechargeable battery’s -

terminal, and B2b (red) to the rechargeable battery’s +

terminal.

3. Connect B3a (black) to the second rechargeable battery’s -

terminal, and B3b (red) to the second rechargeable

battery’s + terminal.

Bosch Sicherheitssysteme GmbH F.01U.097.252 | V 3.2 | 2010.01

12 en AEC-AMC2-UL1 - Installation manual

F.01U.097.252 | V 3.2 | 2010.01 Bosch Sicherheitssysteme GmbH

i

NOTICE!

To switch the power supply between 12 V or 24 V modes,

disconnect the input voltage and set the switch as shown in the

figure below.