Dell PowerEdge C8000: Connecting the Server Enclosure to a Rack PDU To connect a single server enclosure to the PDU:

Connecting the Server Enclosure to a Rack PDU To connect a single server enclosure to the PDU:: Dell PowerEdge C8000

Table of contents

Connecting the Server Enclosure to a Rack PDU

WARNING:

Do not connect or disconnect power cables to the PDU device while

the PDU is energized. Turn off the PDU breaker switches to avoid potentially

serious or fatal electrical shock. Move the PDU A, B, and C breaker switches to

the "OFF" position.

1

Unlock the cable cover

.

2

Rotate the cover

back and away from the PDU.

3

Attach the server enclosure(s) power cables to the PDU power bus bar.

NOTE:

The PDU device supports a maximum of five PowerEdge C8000 server

enclosures depending on the system configuration and power budget.

To connect a single server enclosure to the PDU:

a

Secure the three black power cable lugs

to the top power bus bar

(GND) with the three screws

.

b

Secure the three yellow power cable lugs

to the bottom power bus

bar with the three screws

.