Dell PowerEdge R415: Environmental
Environmental: Dell PowerEdge R415
Table of contents
- Notes, Cautions, and Warnings
- Installation and Configuration Unpacking the System Installing the Rails and System in a Rack
- Optional – Connecting the Keyboard, Mouse, and Monitor Connecting the Power Cable(s)
- Installing the Power Cord Retention Bracket Turning On the System
- Installing the Optional Bezel Complete the Operating System Setup Supported Operating Systems
- Other Information You May Need
- Obtaining Technical Assistance Technical Specifications Processor Expansion Bus Memory
- Drives Connectors Video
- Power Physical
- Environmental
- Environmental (continued)

Environmental
NOTE: For additional information about environmental measurements for specific
system configurations, see dell.com/environmental_datasheets.
Temperature
Operating
10° to 35°C (50° to 95°F) with a maximum
temperature gradation of 10°C per hour
NOTE: For altitudes above 2950 feet, the
maximum operating temperature is derated
1ºF/550 ft.
Storage
–40° to 65°C (–40° to 149°F) with a
maximum temperature gradation of 20°C
per hour
Relative humidity
Operating
20% to 80% (noncondensing) with a
maximum humidity gradation of 10%
per hour
Storage
5 to 95% (noncondensing) with a maximum
humidity gradation of 10% per hour
Maximum vibration
Operating
0.26 Grms at 5–350 Hz for 15 min
Storage
1.87 Grms at 10–500 Hz for 15 min
Maximum shock
Operating
One shock pulse in the positive z axis
(one pulse on each side of the system) of
31 G for 2.6 ms in the operational orientation
Storage
Six consecutively executed shock pulses in
the positive and negative x, y, and z axes
(one pulse on each side of the system) of
71 G for up to 2 ms, and Square Wave 32G,
270 in/sec
Getting Started With Your System 11