Dell UPS 10000R: Installing the Input and Ground Wires

Installing the Input and Ground Wires: Dell UPS 10000R

Table of contents

Installing the Input and Ground Wires

1

2

3

4

Pull the input wire through the conduit, leaving a pproximately 2 ft (0.5m) of exposed wire. Attach

a flexible metal fitting to the end of the conduit.

5

Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.

Strip 0.5 (1.5 cm) of insulation from the end of each i ncoming wire.

6

Connect the input and ground wires to the terminal block according to the UPS Wiring

Specifications in the following table.

Terminal

Terminal Wire

Wire Function

UPS Wire Function

Tightening Torque

Position

Size Rating*

Input

1

Input Ground

2

16–35 mm

2

L2/Neutral In

1.7 Nm (15 lb-in)

(8–2 AWG)

3

L1 In

* Use a minimum:

S 8 AWG for equipment grounding wire, 75_C copper wire minimum

S 4 AWG for input line and neutral wires, 75_C copper wire minimum

7

Replace the terminal block cover.

Installation and Startup

|

21