Dell UPS 10000R: Hardwiring the UPS Input

Hardwiring the UPS Input: Dell UPS 10000R

Table of contents

Hardwiring the UPS Input

WARNING:

Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall

perform the electrical installation.

The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following

requirements:

S

Protection device requires a two-pole disconnection device between the UPS input and the mains

S

Breaker must be wall-mounted and be readily accessible to the operator

S

For Europe. Breaker must meet the IEC/EN 60934 standard and at least 3 mm contact air gap

S

200–240 Vac

S

Single-phase

S

50/60 Hz

S

Flexible metal conduit (recommended for ease of service and maintenance)

Wall

2-pole

Breaker

Line

AC Mains

UPS

Neutral/L2

18

|

Installation and Startup