Dell UPS 5600R: Hardwiring the UPS Input

Hardwiring the UPS Input: Dell UPS 5600R

Hardwiring the UPS Input

WARNING: Only qualified service personnel (such as a licensed electrician) shall perform the electrical

installation. Risk of electrical shock.

The UPS requires a dedicated branch circuit that meets the following requirements:

S The protection device requires a two-pole disconnection device between the UPS output and the

load (see Figure 4)

S The breaker must be wall-mounted and be readily accessible to the operator

S For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at

least 3 mm

S 200–240 Vac

S Single-phase

- 5600W/208V model is phase-to-phase

- 5600W/230V model is phase-to-neutral

S 50/60 Hz

S Flexible metal conduit (recommended for ease of service and maintenance)

Wall

2-pole

Breaker

Line

AC Mains

UPS

Neutral/L2

Figure 4. Circuit Breaker Diagram

16

|

Installation and Startup