Product Specifications

The Dell Managed Rack PDU distributes power to the devices in the rack.

OUTLETS The Rack PDU has twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19 outlets.

P

OWER CORD The 3.0 m (10 ft) power cord terminates with an IEC-309, 32 A 3-pin plug (332P6W).

J523N

Electrical

Input connection IEC-309, 32 A 3-pin plug

Acceptable input voltage 220–240 VAC +6%, -10%

Maximum input current (phase) 32 A

Input frequency 50/60 Hz

Input power 7.7 kVA

Output voltage 220–240 VAC (Line-to-Neutral)

Output connections Twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19

Maximum output current (outlet) IEC-320-C19: 16A; IEC-320-C13: 10A

Maximum output current (phase) 32 A

Maximum output current (breaker) 16 A

Overload protection (internal) Two (2) 16 A, 1-pole hydraulic-magnetic circuit breakers

Physical

182.9 x 5.6 x 5.5 cm

Dimensions

(72.0 x 2.2 x 2.16 in)

(H x W x D)

Depth at breakers: 9.4 cm (3.7 in.)

Shipping dimensions

207.9 x 22.5 x 15.6 cm

(H x W x D)

(81.9 x 8.9 x 6.1 in)

Weight 8.9 kg (19.5 lb)

Shipping weight 9.3 kg (20.5 lb)

Environmental

Maximum elevation

(above MSL)

Operating

0 to 3 048 m (0 to 10,000 ft)

Storage

0 to 15 240 m (0 to 50,000 ft)

Temperature

0 to 50°C (32 to 122°F)

Operating

Storage

-15 to 60°C (5 to 140°F)

Humidity

5 to 95%, non-condensing

Operating

Storage

5 to 95%, non-condensing