Rothenberger ROTEST GW 150/4: инструкция

Раздел: Измерительные инструменты

Тип:

Инструкция к Rothenberger ROTEST GW 150/4

ROTEST GW 150/4

ROTEST GW 150/4

Bedienungsanleitung

Instructions for use

Instruction d’utilisation

Instrucciones de uso

Istruzioni d’uso

Gebruiksaanwijzing

Instruções de serviço

Brugsanvisning

Bruksanvisning

Bruksanvisning

61700

Käyttöohje

Instrukcja obslugi

61701

Návod k používání

Kullanim kilavuzu

Kezelési útmutató

Οδηγίες χρήσεως

Инструкция по использованию

www.rothenberger.com

A

Overview

8 9 10

7

12

B

5

17

C

16

D

2

3

35

A

37

15

22*

21

36

13

6

14

B

Technical Data

Intro

DEUTSCH - Originalbetriebsanleitung!

Seite 2

Bedienungsanleitung bitte lesen und aufbewahren! Nicht wegwerfen!

Bei Schäden durch Bedienungsfehler erlischt die Garantie! Technische Änderungen vorbehalten!

ENGLISH

page 9

Please read and retain these directions for use. Do not throw them away! The warranty does not cover

damage caused by incorrect use of the equipment! Subject to technical modifications!

page 15

FRANÇAIS

Lire attentivement le mode d’emploi et le ranger à un endroit sûr! Ne pas le jeter ! La garantie est

annulée lors de dommages dûs à une manipulation erronée ! Sous réserve de modifications techniques!

ESPAÑOL

página 22

¡Por favor, lea y conserve el manual de instrucciones! ¡No lo tire! ¡En caso de daños por errores de

manejo, la garantía queda sin validez! Modificaciones técnicas reservadas!

ITALIANO

pagina 28

Per favore leggere e conservare le istruzioni per l´uso! Non gettarle via! In caso di danni dovuti ad errori

nell´uso, la garanzia si estingue! Ci si riservano modifiche tecniche!

NEDERLANDS

bladzijde 35

Lees de handleiding zorgvuldig door en bewaar haar goed! Niet weggooien! Bij schade door

bedieningsfouten komt de garantieverlening te vervallen! Technische wijzigingen voorbehouden!

PORTUGUES

pagina 42

Queiram ler e guardar o manual de instruções! Não deitar fora! Em caso de avarias por utilização

incorrecta, extingue-se a garantia! Reservado o direito de alterações técnicas!

DANSK

side 49

Læs betjeningsvejledningen, og gem den til senere brug! Smid den ikke ud! Skader, som måtte opstå som

følge af betjeningsfejl, medfører, at garantien mister sin gyldighed! Ret til tekniske ændringer forbeholdes!

SVENSKA

sida 55

Läs igenom bruksanvisningen och förvara den väl! Kasta inte bort den! Garantin upphör om apparaten

har använts eller betjänats på ett felaktigt sätt! Med reservation för tekniska ändringar!

NORSK

side 61

Les bruksanvisningen og oppbevar den vel! Ikke kast den! Oppstår skader på grunn av betjeningsfeil

opphører garantiens gyldighet! Tekniske forandringer forbeholdes!

SUOMI

sivulta 67

Lue ja säilytä tämä käyttöohje! Älä heitä pois!

Takuu ei kata käyttövirheistä aiheutuvia vahinkoja! Oikeudet teknisiin muutoksiin pidätetään!

POLSKI

strony 73

Instrukcjê obslugi prosze przeczytac i przechowac! Nie wyrzucac!

Przy uszkodzeniach wynikajacych z blêdów obslugi wygasa gwarancja! Zmiany techniczne zastrzezone!

CESKY

stránky 80

Návod k obsluze si prosím prectete a uschovejte jej! Nevyhazujte jej!

V prípade poškození zpusobeném chybnou obsluhou zaniká záruka! Technické zmeny jsou vyhrazeny!

TÜRKÇE

sayfa 86

Kullanim açiklamalarini lütfen dikkatlice okuyunuz ve bir yerde muhafaza ediniz! Çöpe atmayiniz!

Kullaniminda yapilan hatalar, garantinin silinmesine neden olur! Teknik deðiþiklikler yapma hakkimiz saklidir!

MAGYAR

oldaltól 93

Kérjük, olvassa el és õrizze meg a kezelési utasítást! Ne dobja el!

A helytelen kezelésbõl származó károsodások esetén megszûnik a jótállás! Mûszaki változtatások fenntartva!

ΕΛΛΗΝΙΚΑ

100Σελίδα

Οδηγίες χειρισμού παρακαλείσθε να τις διαβάσετε και να τις φυλάσσετε! Μην τις πετάξετε!

Σε ζημιες από σφάλματα χειρισμού παυει να ισχύει η εγγύηση! Με επιφύλαξη για τεχνικές αλλαγές!

PУCCKИЙ

Страница 107

Прочтите инструкцию по эксплуатации и сохраняйте её для дальнейшего использования! B случае поломки инструмента

из-за несоблюдения инструкции клиент теряет право на обслуживание по гарантии! Bозможны технические изменения!

1

Inhalt Seite

1 Hinweise zur Sicherheit 3

1.1 Bestimmungsgemäßer Gebrauch 3

1.2 Hinweise zur Sicherheit von Mensch und Gerät 3

2 Einzelteile und Bedienelemente des ROTEST GW 150/4 (Abb.A) 3

3 Technische Daten 4

4 Eigenprüfung als Funktionssicherheitsprüfung 4

4.1 Eigenprüfung mit Handpumpe (3) und Verbindungsschlauch (6) 4

4.2 Eigenprüfung mit Einfachgebläse (12), Wassersäule und

Verbindungsschlauch (6) 4

5 Bedienung und Durchführung von Prüfungen mit dem ROTEST GW 150/4 5

5.1 Belastungsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600) 5

5.2 Dichtheitsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600) 5

5.3 Einstellung des Düsenvordruckes an atmosphärischen- und Gebläsebrennern

mit Wassersäule bis 30 mbar 6

5.4 Vorprüfung von Trinkwasser-Hausinstallationen 6

5.5 Hauptprüfung von Trinkwasser-Hausinstallationen 7

6 Prüfprotokoll 7

7 Außerbetriebnahme 7

8 Wartung und Pflege 8

9 Zubehör 8

10 Entsorgung 8

Kennzeichnungen in diesem Dokument

Gefahr

Dieses Zeichen warnt vor Personenschäden.

Achtung

Dieses Zeichen warnt vor Sach- oder Umweltschäden.

Aufforderung zu Handlungen

2 DEUTSCH

1 Hinweise zur Sicherheit

1.1 Bestimmungsgemäßer Gebrauch

Das Prüfgerät ROTEST GW 150/4 mit seinen zugehörigen Elementen (im Koffer beiliegend) darf

ausschließlich von Fachpersonal mit Kenntnissen der Versorgungstechnik für Dichtheitsprüfungen

von Rohrleitungen und Behältern gemäß der folgenden Anleitung verwendet werden. Dies betrifft

insbesondere folgende Einsatzbereiche:

Belastungsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600, April 2008)

Dichtheitsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600, April 2008)

Eigenprüfung als Funktionssicherheitsprüfung mit Handpumpe, Verbindungsschlauch und

Adapter mit Absperrventil

Eigenprüfung als Funktionssicherheitsprüfung mit Einfachgebläse, Wassersäule,

Verbindungsschlauch und Absperrventil

Dichtheitsprüfung für Propan-Flüssiggasleitungen mit Wassersäule bis 150 mbar und

Niederdruck-Flüssiggasleitungen mit Wassersäule bis 60 mbar

Einstellung des Düsenvordruckes an atmosphärischen- und Gebläsebrennern mit Wassersäule

bis 30 mbar

Überprüfung des Geräteanschlussdruckes an Gasgeräten mit Wassersäule bis 30 mbar

Vorprüfung und Hauptprüfung von Trinkwasser-Hausinstallationen nach DIN 1988 (TRWI) mit

Luft

1.2 Hinweise zur Sicherheit von Mensch und Gerät

Führen Sie keinerlei Arbeiten in Inneren des Gerätes aus! In diesem Bereich darf

ausschließlich geschultes Fachpersonal (Kundendienst) tätig werden!

Befolgen Sie die Sicherheitshinweise des Anlagen- bzw. Rohrherstellers sowie die

Hinweise zur Sicherheit der Hersteller der Verbindungselemente!

2 Einzelteile und Bedienelemente des ROTEST GW 150/4 A

2 Tank 10 Steckrohr (121-155 mbar) 21 Adapter für Gasgeräte

3 Handpumpe 12 Einfachgebläse 22* Einrohrzählerkappe

5 Manometer 13 Gasprüfstopfen Gr. 0 konisch 35 Pflegefett für O-Ringe

6 Verbindungsschlauch 14 Gasprüfstopfen Gr. 1 konisch 36 O-Ringe

7 Steckrohr festinstalliert 15 Gasprüfstopfen Gr. 2 konisch 37 Betriebsanleitung

8 Steckrohr (41–75 mbar) 16 Gasprüfstopfen Gr. 1 zylindrisch

9 Steckrohr (81-115 mbar) 17 Gasprüfstopfen Gr. 2 zylindrisch

* = Zubehör bei Ausführung 6.1701

DEUTSCH 3

3 Technische Daten

Prüfgenauigkeit Manometer 0,1 bar (Anzeigenbereich 0 – 4 bar)

Wassersäule gemäß TRGI mit einer Ablesegenauigkeit von

0,1mbar.

Befüllung des Wassertanks Das Gerät wird mit gefülltem Wassertank (2) angeliefert. Sollte

Wasser nicht in ausreichender Menge im Tank sein, siehe Abb. B.

Sie dürfen weder destilliertes Wasser noch Wasser mit Zusätzen wie Alkohol, Spiritus

oder ähnliches zur Befüllung verwenden! Dadurch verändert sich die

Oberflächenspannung der Flüssigkeit und die Messergebnisse werden verfälscht. Bei

Temperaturen unter 0 °C, darf das Gerät nicht eingesetzt werden. Es besteht die

akute Gefahr von Frostschäden am Wasserbehälter, den Absperrventilen und den

Steckrohren.

Hierfür übernimmt ROTHENBERGER keine Gewährleistung.

4 Eigenprüfung als Funktionssicherheitsprüfung

Vor Inbetriebnahme des Gerätes – bzw. in regelmäßigen zeitlichen Abständen – ist die

Funktionssicherheit des Gerätes durch eine Eigenprüfung zu kontrollieren und sicherstellen.

4.1 Eigenprüfung mit Handpumpe (3) und Verbindungsschlauch (6)

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss A.

Bringen Sie das System durch Pumpen mit der Handpumpe auf einen Prüfdruck von 3 bar.

Warten Sie den Temperaturausgleich über eine Zeit von 10 Minuten ab, um der

eingebrachten Luft die Möglichkeit zur Erwärmung oder Abkühlung zu geben.

Bei größeren Temperaturänderungen ist die Ausgleichszeit zu verlängern!

Führen Sie die Prüfung über eine Prüfzeit von 10 Minuten durch. Während dieser Zeit darf der

angezeigte Druck nicht fallen.

4.2 Eigenprüfung mit Einfachgebläse (12), Wassersäule und Verbindungsschlauch (6)

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss B.

Montieren Sie Steckrohrsystem wie folgt:

- Schieben Sie das Steckrohr (8) mit der Skala 41-75 mbar durch leichte Drehung in das

fest installierte Steckrohr (7).

- Schieben Sie nun das Steckrohr (9) mit der Skala 81-115 mbar durch leichte Drehung in

das Steckrohr (8).

Öffnen Sie die Absperrventile der Anschlüsse B, C und D.

Bringen Sie das System durch Pumpen mit dem Einfachgebläse (12) auf den Prüfdruck von

110 mbar.

Schließen Sie das Absperrventil von Anschluss C, da sonst ein Druckabfall eintreten kann.

Warten Sie den Temperaturausgleich über eine Zeit von 10 Minuten ab, um der

eingebrachten Luft die Möglichkeit zur Erwärmung oder Abkühlung zu geben.

Bei größeren Temperaturänderungen ist die Ausgleichszeit zu verlängern!

Führen Sie die Prüfung über eine Prüfzeit von 10 Minuten durch. Während dieser Zeit darf der

angezeigte Druck nicht fallen.

4 DEUTSCH

5 Bedienung und Durchführung von Prüfungen mit dem ROTEST GW 150/4

5.1 Belastungsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600)

Folgende Punkte sind zu berücksichtigen:

Die Belastungsprüfung ist bei neu verlegten Leitungen ohne Armaturen durchzuführen.

Für die Dauer der Prüfung müssen alle Leitungsöffnungen mit Stopfen, Kappen,

Steckscheiben oder Blindflanschen aus metallenen Werkstoffen dicht verschlossen sein.

Verbindungen mit gasführenden Leitungen sind unzulässig.

Führen Sie die Belastungsprüfung durch, bevor die Leitungen verputzt oder verdeckt und ihre

Verbindungen beschichtet oder umhüllt sind.

Sollte die Prüfung vom Anschluss für einen Gaseinrohrzähler her erfolgen, wird die Leitung

am Anschlussventil mit der Einrohrzählerkappe mit Gewindeanschluss (22) verschlossen.

Gehen Sie wie folgt vor:

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss A.

Setzen Sie einen passenden Prüfstopfen in das offene Leitungsende ein und bringen Sie den

Stopfengummi durch Drehen der Flügelmutter zur Ausdehnung, bis der Stopfen festsitzt und

dicht ist.

Stecken Sie das freie Ende des Verbindungsschlauches (6) auf den Anschluss am Prüfstopfen.

Bringen Sie das System durch Pumpen mit der Handpumpe auf einen Prüfdruck von 1 bar.

Warten Sie den Temperaturausgleich über eine Zeit von 10 Minuten ab, um der

eingebrachten Luft die Möglichkeit zur Erwärmung oder Abkühlung zu geben.

Bei starken Temperatur- oder Luftdruckänderungen reichen 10 Minuten nicht aus! In

Abhängigkeit von Temperatur- oder Druckänderungen kann die Ausgleichszeit bis zu

zwei Stunden dauern!

Führen Sie die Prüfung über eine Prüfzeit von 10 Minuten durch. Während dieser Zeit darf der

angezeigte Druck nicht fallen.

5.2 Dichtheitsprüfung von Gas-Hausinstallationen gemäß DVGW-TRGI (G600)

Für Propan-Flüssiggasleitungen mit Wassersäule bis 150 mbar

Für Niederdruck Flüssiggasleitungen mit Wassersäule bis 40-60 mbar

Folgende Punkte sind zu berücksichtigen:

Die Dichtheitsprüfung erstreckt sich auf die Leitungen einschließlich der Armaturen, jedoch

ohne Gasgeräte sowie zugehörige Regel- und Sicherheitseinrichtungen.

Verbindungen mit gasführenden Leitungen sind unzulässig.

Die Dichtheitsprüfung ist durchzuführen, bevor die Leitungen verputzt oder verdeckt und ihre

Verbindungen beschichtet oder umhüllt sind.

Der Gaszähler kann in die Dichtheitsprüfung mit einbezogen werden.

Erfolgt die Prüfung vom Anschluss für einen Gaseinrohrzähler, verschließen Sie die Leitung am

Anschlussventil mit einer Einrohrzählerkappe mit Gewindeanschluss (22).

Gehen Sie wie folgt vor:

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss B.

Setzen Sie einen passenden Prüfstopfen in das offene Leitungsende ein und bringen Sie den

Stopfengummi durch Drehen der Flügelmutter zur Ausdehnung, bis der Stopfen festsitzt und

dicht ist.

Stecken Sie das freie Ende des Verbindungsschlauches (6) auf den Anschluss am Prüfstopfen.

DEUTSCH 5

Montieren Sie das Steckrohrsystem wie folgt:

- Schieben Sie das Steckrohr (8) mit der Skala 41-75 mbar durch leichte Drehung in das

fest installierte Steckrohr (7).

- Schieben Sie nun das Steckrohr (9) mit der Skala 81-115 mbar durch leichte Drehung in

das Steckrohr (8).

- Schieben Sie jetzt das Steckrohr (10) mit der Skala 121-155 mbar durch leichte Drehung

in das Steckrohr (9)

Öffnen Sie die Absperrventile der Anschüsse B, C und D.

Bringen Sie das System durch Pumpen mit dem Einfachgebläse (12) auf den Prüfdruck von

150 mbar.

Schließen Sie das Absperrventil von Anschluss C, da sonst ein Druckabfall eintreten kann.

Warten Sie den Temperaturausgleich über eine Zeit von 10-60 Minuten (abhängig vom

Leitungsvolumen) ab, um der eingebrachten Luft die Möglichkeit zur Erwärmung oder

Abkühlung zu geben.

Bei starken Temperatur- oder Luftdruckänderungen reichen 10-60 Minuten

nicht aus! In Abhängigkeit von Temperatur- oder Druckänderungen kann die

Ausgleichszeit bis zu zwei Stunden dauern!

Führen Sie die Prüfung über eine Prüfzeit von 10-30 Minuten (abhängig vom

Leitungsvolumen) durch. Während dieser Zeit darf der angezeigte Druck nicht fallen.

Dichtheitsprüfung: Anpassungszeiten und Prüfdauer in Abhängigkeit vom Leitungsvolumen

Leitungsvolumen* Anpassungszeit mind. Prüfdauer

< 100 l 10 min. 10 min.

100 l < 200l 30 min. 20 min.

200l 60 min. 30 min.

*Richtwerte

5.3 Einstellung des Düsenvordruckes an atmosphärischen- und Gebläsebrennern

mit Wassersäule bis 30 mbar

Gehen Sie wie unter Pkt. 5.2 vor:

Ein fest installiertes Steckrohr (7) bis 30 mbar ist hierfür ausreichend.

Schließen Sie den Adapter für Gasgeräte (21) an das freie Ende des Verbindungsschlauches

(6) an.

Stecken Sie die Tülle des Adapters für Gasgeräte (21) auf den Prüfanschluss für den

Düsenvordruck Ihres Gasbrenners auf.

Stellen Sie das Gasgerät so an, dass der Brenner mit voller Brennbelastung läuft.

Öffnen Sie die Absperrventile der Anschlüsse B und D.

Lesen Sie jetzt den tatsächlich vorhandenen Düsenvordruck ab.

5.4 Vorprüfung von Trinkwasser-Hausinstallationen

Gehen Sie wie folgt vor:

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss A.

Stecken Sie das freie Ende des Verbindungsschlauches (6) mit hörbarem Rastgeräusch auf den

Stecknippel Ihres Adapters am Rohrende.

Bringen Sie das System durch Pumpen mit der Handpumpe (3)

- bei Nennweiten bis DN 50 auf einen Prüfdruck von maximal 3 bar

- bei Nennweiten über DN 50 bis DN 100 auf einen Prüfdruck von max. 1 bar.

6 DEUTSCH

Warten Sie den Temperaturausgleich über eine Zeit von 10 Minuten ab, um der

eingebrachten Luft die Möglichkeit zur Erwärmung oder Abkühlung zu geben.

Bei starken Temperatur- oder Luftdruckänderungen reichen 10 Minuten nicht aus! In

Abhängigkeit von Temperatur- oder Druckänderungen kann die Ausgleichszeit bis zu

zwei Stunden dauern!

Führen Sie die Prüfung über eine Prüfzeit von 10 Minuten durch. Während dieser Zeit darf der

angezeigte Druck nicht fallen.

5.5 Hauptprüfung von Trinkwasser-Hausinstallationen

Gehen Sie wie folgt vor:

Schließen Sie sämtliche Absperrventile Ihres ROTEST GW 150/4.

Stecken Sie den Verbindungsschlauch (6) mit hörbarem Rastgeräusch auf den Stecknippel von

Anschluss B.

Setzen Sie einen passenden Prüfstopfen in das offene Leitungsende ein und bringen Sie den

Stopfengummi durch Drehen der Flügelmutter zur Ausdehnung, bis der Stopfen festsitzt und

dicht ist.

Stecken Sie das freie Ende des Verbindungsschlauches (6) auf den Anschluss am Prüfstopfen.

Montieren Sie das Steckrohrsystem wie folgt:

- Schieben Sie das Steckrohr (8) mit der Skala 41-75 mbar durch leichte Drehung in das

fest installierte Steckrohr (7).

- Schieben Sie nun das Steckrohr (9) mit der Skala 81-115 mbar durch leichte Drehung in

das Steckrohr (8).

Öffnen Sie die Absperrventile der Anschlüsse B, C und D.

Bringen Sie das System durch Pumpen mit dem Einfachgebläse (12) auf den Prüfdruck von

110 mbar.

Schließen Sie das Absperrventil von Anschluss C, da sonst ein Druckabfall eintreten kann.

Warten Sie den Temperaturausgleich über eine Zeit von 10 Minuten ab, um der

eingebrachten Luft die Möglichkeit zur Erwärmung oder Abkühlung zu geben.

Bei starken Temperatur- oder Luftdruckänderungen reichen 10 Minuten nicht aus! In

Abhängigkeit von Temperatur- oder Druckänderungen kann die Ausgleichszeit bis zu

zwei Stunden dauern!

Führen Sie die Prüfung

- bis zu 100 Liter Leitungsvolumen über eine Prüfzeit von mindestens 30 Minuten durch.

Erhöhen Sie die Prüfzeit

- für je weitere 100 Liter Leitungsvolumen um 10 Minuten.

6 Prüfprotokoll

Der verantwortliche Fachmann muss nach Beendigung der jeweiligen Prüfung ein Druckprotokoll

erstellen.

7 Außerbetriebnahme

Demontieren Sie nach der Dichtheitsprüfung den Verbindungsschlauch (6) und öffnen Sie das

Absperrventil am Anschluss D, damit die Wassersäule in den Tank (2) ablaufen kann.

Demontieren Sie die Steckrohre und plazieren diese an ihrem vorgesehenen Platz im

Stahlblechkoffer Ihres ROTEST GW 150/4.

Schließen Sie alle Absperrventile und klappen Sie die Pumpe ein.

DEUTSCH 7

8 Wartung und Pflege

Versehen Sie regelmäßig mit dem beiliegenden Silikon-Pflegefett die O-Ringe der Steckrohre, die

Steckkupplungen und die Gaszählerkappe!

Versehen Sie auch die Rohraufweitungen an den Steckrohren innen mit Fett, um die Montage zu

erleichtern!

Lagern Sie den Stahlblechkoffer sauber und trocken, damit innenliegende Teile nicht korrodieren!

Korrosion an den Ventilen beeinträchtigt deren Funktion!

Behandeln Sie den ROTEST GW 150/4 mit Sorgfalt!

9 Zubehör

Geeignetes Zubehör und ein Bestellformular finden Sie ab Seite 114.

10 Entsorgung

Teile des Gerätes sind Wertstoffe und können der Wiederverwertung zugeführt werden.

Hierfür stehen zugelassene und zertifizierte Verwerterbetriebe zur Verfügung. Zur

umweltverträglichen Entsorgung der nicht verwertbaren Teile (z.B. Elektronikschrott) befragen Sie

bitte Ihre zuständige Abfallbehörde.

8 DEUTSCH

Contens Page

1 Safety instructions 10

1.1 Proper use 10

1.2 Operator and equipment safety 10

2 Components and Operator Controls (fig. A) 10

3 Technical data 11

4 Built-in safety tests 11

4.1 Built-in hand pump (3) and connecting hose (6) test 11

4.2 Built-in bellow (12), water column and connecting hose (6) test 11

5 Operating and performing tests with the ROTEST GW 150/4 12

5.1 Bearing test of gas fittings pursuant to 1* 12

5.2 Leak test of gas fittings pursuant to 1* 12

5.3 Adjustment of gas admission pressure to atmospheric and blower

burners using water column up to 30 mbar 13

5.4 Initial test of drinking water systems of domestic connections 13

5.5 Principle test of drinking water systems for domestic connections

pursuant to 1* 14

6 Test protocol 14

7 Disassembly 14

8 Maintenance and care 14

9 Accessories 14

10 Disposal 14

Markings in this document

Danger

This sign warns against the danger of personal injuries.

Caution

This sign warns against the danger of property damage and damage to the

environment.

Call for action

1* Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

ENGLISH 9

1 Safety instructions

1.1 Proper use

The ROTEST GW 150/4 test instrument and its components (included in carrying case) should only

be operated by skilled personnel competent in gas and water supply engineering in particular in

leakage tests for pipes and containers. All tests must be carried out in accordance with the

present instructions, in particular the following tests:

Bearing tests for gas fittings pursuant to 1*

Leak tests of gas fittings pursuant to 1*

Built-in hand pump, connecting hose and adapter with cut-off valve safety tests

Built-in bellow, water column, connecting hose and cut-off valve safety tests

Leak test of propane liquid gas fittings and low-pressure liquid gas fittings pursuant to 1*

Adjustment of gas admission pressure to atmospheric and blower burners using a water

column up to 30 mbar

Examination and inspection of gas appliance connection pressure pursuant to 1*

Initial air-and principle air-pressure test of drinking water systems pursuant to 1*

1.2 Operator and equipment safety

Do not open test instrument! Do not attempt to repair the internal components! Ask

your dealer for a list of qualified service technicians!

Follow all safety instructions specified by the systems or pipe manufacturers as well as

the safety instructions specified by the pipe coupling manufacturer!

2 Components and Operator Controls A

2 tank 10 tube element (121-155 mbar) 21 adapter for gas

appliances

3 hand pump 12 bellow 22* supply-end cap

5 manometer 13 conical gas test plug, size 0 35 silicon lubricant

6 connecting hose 14 conical gas test plug, size 1 36 O ring (spare)

7 tube element (fixed) 15 conical gas test plug, size 2 37 instruction manual

8 tube element (41-75 mbar) 16 cylindrical gas test plug, size 1

9 tube element (81-115 mbar) 17 cylindrical gas test plug, size 2

* = accessorie with version 6.1701

1* Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

10 ENGLISH

3 Technical data

Accuracy manometer 0.1 bar (display range 0 - 4 bar) water column with

a reading accuracy of 0.1 mbar pursuant to 1*

Filling water tank The ROTEST GW 150/4 is supplied with a full water tank (2).

Should the tank need refilling, see fig. B.

Do not use distilled water or water with any additives, such as alcohol, spirits or any

other similar substances! Additives will change the surface tension of the liquid used

and adulterate test readings! Do not use the ROTEST GW 150/4 in an environment

under 0°C (32°F)! Using the instrument in frozen or freezing environments may cause

damage to the water tank, the cut-off valves and the couplings.

ROTHENBERGER cannot and will not accept any warranty claims arising from

negligence or failure to adhere to these instructions.

4 Built-in safety tests

Carry out the safety tests integrated in the ROTEST GW 150/4 before commissioning the

instrument and in regular intervals. Ensure that the instrument is functions properly before use.

4.1 Built-in hand pump (3) and connecting hose (6) test

Close all cut-off valves on your ROTEST 150/4.

Insert connecting hose (6) to connecting valve A. An auditable sound is heard when hose

and valve nipple are properly locked.

Use hand pump to increase system pressure to 3 bar.

Wait 10 minutes for loaded air and water temperatures to equalize.

Prolong period of temperature equalization if temperatures fluctuate greatly!

Carry out test over a period of ten minutes. The indicated pressure should not drop over a 10-

minute period.

4.2 Built-in bellow (12), water column and connecting hose (6) test

Close all cut-off valves on your ROTEST GW 150/4.

Insert connecting hose (6) to connecting valve B. An auditable sound is heard when hose

and valve nipple are properly locked.

Assemble tube element system as follows:

- while carefully turning insert tube element (8) with scale 41-75mbar into fixed tube

element (7).

- while carefully turning insert tube element (9) with scale 81-115mbar into tube element (8)

Open connecting valves B,C and D.

Use bellow (12) to load a pressure of 110 mbar into the test system.

Close connecting valve C to avoid a loss in pressure.

Wait 10 minutes for loaded air and water temperatures to equalize.

Prolong period of temperature equalization if temperatures fluctuate greatly!

Carry out test over a period of ten minutes. The indicated pressure should not drop over a 10-

minute period.

1* Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

ENGLISH 11

5 Operating and performing tests with the ROTEST GW 150/4

5.1 Bearing test of gas fittings pursuant to 1*

The following aspects must be taken into careful consideration:

All bearing tests are to be performed on newly fitted gas pipe systems without fixtures.

All pipe openings must be sealed off with plugs, caps, blanks or blind flanges for the duration

of the test.

The system must be isolated from all other gas carrying systems.

Carry out all bearing tests before the pipes are plastered or covered and the joints are coated

or jacketed.

If the test is to be carried out at the gas meter end of the pipe system, use the threaded

supply-end cap (22) to seal off the pipe system.

Complete test as follows:

Close all cut-off valves on your ROTEST GW 150/4.

Insert connecting hose (6) to connecting valve A. An auditable sound is heard when hose

and valve nipple are properly locked.

Insert an appropriate test plug into the open end of the pipe and seal off end by turning the

wing nut until the pipe is sealed tight.

Insert the open end of the connecting hose (6) to the valve on the test plug.

Use the hand pump to load a pressure pursuant to 1* to the pipe system.

Wait 10 minutes for loaded air and water temperatures to equalize.

Prolong 10-minute period of temperature equalization if temperatures

fluctuate greatly. The equalization period can last up to two hours!

Carry out the test over a period prescribed by 1*. Over this period the pressure indicated must

not drop.

5.2 Leak test of gas fittings pursuant to 1*

For propane liquid gas fittings and low-pressure liquid gas fittings pursuant to 1*

The following aspects must be taken into careful consideration:

The leak test gas fitting includes all fixtures, but not gas appliances as well as the associated

control and safety devices.

The system must be isolated from all other gas carrying systems.

Carry out all leak tests before the pipes are plastered or covered and the joints are coated or

jacketed.

The gas meter may be included in leak tests.

If the test is to be carried out at the gas meter end of the pipe system, use the threaded

supply-end cap (22) to seal off the pipe system.

Complete test as follows:

Close all cut-off valves on your ROTEST GW 150/4.

Insert connecting hose (6) to connecting valve B. An auditable sound is heard when hose

and valve nipple are properly locked.

Insert an appropriate test plug into the open end of the pipe and seal off end by turning the

wing nut until the pipe is sealed tight

Insert the open end of the connecting hose (6) to the valve on the test plug.

1* Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

12 ENGLISH

Assemble tube element system as follows:

- while carefully turning insert tube element (8) with scale 41 - 75 mbar into fixed tube

element (7).

- while carefully turning insert tube element (9) with scale 81-115mbar into tube

element (8).

- while carefully turning insert tube element (10) with scale 121-115mbar into tube

element (9)

Open connecting valves B, C and D

Use bellow (12) to load a pressure pursuant to 1* into the test system.

Close connecting valve C to avoid a loss in pressure.

Wait 10-60 minutes (dependent on pipe volume) for loaded air and water temperatures to

equalize.

Prolong 10-60 minute period of temperature equalization if temperatures fluctuate

greatly. The equalization period can last up to two hours!

Carry out the test over a period prescribed by 1*. Over this period the pressure indicated must

not drop.

5.3 Adjustment of gas admission pressure to atmospheric and blower burners using

water column up to 30 mbar

Complete test as described 5.2:

The fixed tube element (7) up to 30 mbar is sufficient for this test type.

Connect gas appliance adapter (21) to the open end of the connecting hose (6).

Connect the snout of the gas appliance adapter (21) to the test supply system of the gas

appliance.

Set the gas appliance burner to the highest possible setting.

Open connecting valves B and D.

Read the actual gas admission pressure.

5.4 Initial test of drinking water systems of domestic connections

Complete test as follows:

Close all cut-off valves on your ROTEST GW 150/4.

Insert connecting hose (6) to connecting valve A. An auditable sound is heard when hose

and valve nipple are properly locked.

Insert open end of the connecting hose (6) to your adapter of the end of pipe. An auditable

sound is heard when hose and adapter nipple are properly locked.

Use hand pump (3) to load a pressure pursuant to 1* into the test system

Wait 10 minutes for loaded air and water temperatures to equalize.

Prolong 10-minute period of temperature equalization if temperatures fluctuate

greatly. The equalization period can last up to two hours!

Carry out the test over a period prescribed by 1*. Over this period the pressure indicated must

not drop.

1) Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

ENGLISH 13

5.5 Principle test of drinking water systems for domestic connections pursuant to 1*

Complete test as follows:

Close all cut-off valves on your ROTEST GW 150/4.

Insert connecting hose (6) to connecting valve B. An auditable sound is heard when hose

and valve nipple are properly locked.

Insert an appropriate test plug into the open end of the pipe and seal off end by turning the

wing nut until the pipe is sealed tight.

Insert the open end of the connecting hose (6) to the valve on the test plug.

Assemble tube element system as follows:

- while carefully turning insert tube element (8) with scale 41 – 75 mbar into fixed tube

element (7).

- while carefully turning insert tube element (9) with scale 81 – 115 mbar into tube

element (8).

Open connecting valves B, C and D.

Use bellow (12) to load a pressure pursuant to 1* into the test system.

Close connecting valve C to avoid a loss in pressure.

Wait 10 minutes for loaded air and water temperatures to equalize.

Prolong 10-minute period of temperature equalization if temperatures fluctuate

greatly. The equalization period can last up to two hours!

Carry out the test over a period prescribed by 1* Over this period the pressure indicated must

not drop

1) Statutory regulations in the country of use or the respective manufacturer and facility instructions and guidelines

6 Test protocol

The responsible technician must write up a test protocol after completing leakage tests.

7 Disassembly

After completing leakage tests disconnect the connecting hose (6) and open connecting valve D

so that the water column can flow back into the water tank (2).

Disconnect all tube elements and place them back into the carrying case.

Close all valves and fold down hand pump.

8 Maintenance and care

Use silicon lubricant to daub coupling O rings in the tube elements, couplings and supply-end

cap!

Apply lubricant to the inner surface of all tube expansions on the couplings!

Store carrying case in a clean and dry environment to avoid corrosion of case and instrument

components! Any corrosion on the valves impedes valve function!

Handle your ROTEST GW 150/4 leakage test system carefully!

9 Accessories

The relevant accessories and an order form can be found from Page 114 onwards.

10 Disposal

Components of the unit are recyclable material and should be put to recycling.

For this purpose registered and certified recycling companies are available. For an environmental

friendly disposal of the non-recyclable parts (e.g. electronic waste) please contact your local waste

disposal authority.

14 ENGLISH

Sommaire page

1 Remarques concernant la sécurité 16

1.1 Utilisation conforme à la destination 16

1.2 Remarques concernant la sécurité de l'utilisateur et de l'appareil 16

2 Pièces et éléments de service du ROTEST GW 150/4 (fig. A) 16

3 Caractéristiques techniques 17

4 Autocontrôle de sécurité de fonctionnement 17

4.1 Autocontrôle avec pompe à main (3) et tuyau de raccordement (6) 17

4.2 Autocontrôle avec soufflante simple (12), colonne d'eau et tuyau de

raccordement (6) 17

5 Service et réalisation de contrôles avec le ROTEST GW 150/4 18

5.1 Contrôle de résistance des installations domestiques de gaz conformément à

DVGW-TRGI (G600) 18

5.2 Contrôle d'étanchéité des installations domestiques de gaz conformément à

DVGW-TRGI (G600) 18

5.3 Réglage de la pression amont des buses des brûleurs atmosphériques et

à air soufflé avec colonne d'eau jusqu'à 30 mbars 19

5.4 Contrôle préliminaire des installations domestiques d'eau potable 20

5.5 Contrôle principal des installations domestiques d'eau potable 20

6 Procès-verbal de contrôle 21

7 Mise hors service 21

8 Maintenance et entretien 21

9 Accessoires 21

10 Recyclage 21

Pictogrammes contenus dans ce document

Danger

Ce pictogramme signale un risque de blessure pour les personnes.

Attention

Ce pictogramme signale un risque de dommage matériel ou de préjudice pour

l’environnement.

Nécessité d’exécuter une action

FRANÇAIS 15

1 Remarques concernant la sécurité

1.1 Utilisation conforme à la destination

L'appareil de contrôle ROTEST GW 150/4 ainsi que ses éléments (joints dans la mallette) ne doit

être utilisé que par du personnel spécialisé possédant des connaissances en matière de matériel de

servitude destiné aux contrôles d'étanchéité des conduites et des récipients, conformément aux

instructions suivantes. Ceci concerne en particulier les domaines d'utilisation suivants:

Contrôle de résistance des installations domestiques de gaz conformément à DVGW-TRGI

(G 600, 04/08);

Contrôle d'étanchéité des installations domestiques de gaz conformément à DVGW-TRGI

(G600, 04/08);

autocontrôle de sécurité de fonctionnement avec pompe à main, tuyau de raccordement et

adaptateur avec soupape d'arrêt;

autocontrôle de sécurité de fonctionnement avec soufflante simple, colonne d'eau, tuyau de

raccordement et soupape d'arrêt;

Contrôle d'étanchéité des conduites de gaz propane liquéfié avec colonne d'eau jusqu'à 150

mbars et gaz liquéfié basse pression avec colonne d'eau jusqu'à 60 mbars

réglage de la pression amont des buses des brûleurs atmosphériques et à air soufflé avec

colonne d'eau jusqu'à 30 mbars;

vérification de la pression de raccordement des appareils à gaz avec colonne d'eau jusqu'à 30

mbars;

contrôle préliminaire et principal des installations domestiques d'eau potable selon la norme

DIN 1988 (TRWI) avec de l'air;

1.2 Remarques concernant la sécurité de l'utilisateur et de l'appareil

N'effectuez aucune opération à l'intérieur de l'appareil! Seul le personnel spécialisé

formé à cet effet (SAV) est habilité à y accéder!

Respectez les remarques concernant la sécurité formulées par le fabricant de

l'installation, par le fabricant des conduites ainsi que celles émanant du fabricant des

éléments de raccordement!

2 Pièces et éléments de service du ROTEST GW 150/4 A

2

réservoir

10

tube de fixation (121-

21

adaptateur pour

155 mbar)

appareils à gaz

3

pompe à main

12

soufflante simple

22*

capuchon de compteur

monotubulaire

5

répartiteur

13

bouchon d'essai de gaz

35

graisse d'entretien pour

T. 0 conique

joints toriques

d'étanchéité

6

tuyau de

14

bouchon d'essai de gaz

36

joint torique

raccordement

T. 1 conique

d'étanchéité (rechange)

7

tube de fixation

15

bouchon d'essai de gaz

37

mode d'emploi

inamovible

T. 2 conique

8

tube de fixation (41–

16

bouchon d'essai de gaz

75 mbar)

T. 1 cylindrique

9

tube de fixation (81-

17

bouchon d'essai de gaz

115 mbar)

T. 2 cylindrique

* accessoires pour le modèle 6.1701

16 FRANÇAIS

3 Caractéristiques techniques

Fidélité Manomètre 0,1 bar (plage d'affichage 0 – 4 bars)

Colonne d'eau conformément à TRGI avec une précision de

lecture de 0,1 mbar.

Remplissage du réservoir d'eau L'appareil est livré avec un réservoir d'eau plein (2). Si la quantité

d'eau contenue dans le réservoir n'est pas suffisante, voir fig. B

Pour le remplissage, vous ne devez utiliser ni eau distillée ni eau contenant des

additifs tels que de l'alcool ou un produit similaire! Ceci modifierait la tension

superficielle du liquide et fausserait les résultats de mesure. Ne pas utiliser l'appareil

à des températures inférieures à 0 °C. Risque important de dégâts dus au gel pour le

réservoir d'eau, les soupapes d'arrêt et les tubes de fixation.

ROTHENBERGER exclut toute garantie dans ce cas-là.

4 Autocontrôle de sécurité de fonctionnement

Avant sa mise en service, ou bien à intervalles réguliers, vérifiez et assurez la sécurité de

fonctionnement de l'appareil en effectuant un autocontrôle.

4.1 Autocontrôle avec pompe à main (3) et tuyau de raccordement (6)

Fermez toutes les soupapes d'arrêt de votre ROTEST GW 150/4.

Enfoncez le tuyau de raccordement (6) sur l'embout enfichable du raccord A jusqu'à ce que

vous l'entendiez s'enclencher.

En pompant avec la pompe à main, amenez le système à une pression d'essai de 3 bars.

Attendez pendant 10 minutes que les températures s'équilibrent, pour donner à l'air amené la

possibilité de se réchauffer ou de se refroidir.

Prolonger le temps d'équilibrage lorsque les modifications de température sont

importantes!

Effectuez le contrôle pendant une durée de 10 minutes. Pendant ce laps de temps la pression

indiquée ne doit pas retomber.

4.2 Autocontrôle avec soufflante simple (12), colonne d'eau et tuyau de

raccordement (6)

Fermez toutes les soupapes d'arrêt de votre ROTEST GW 150/4.

Enfoncez le tuyau de raccordement (6) sur l'embout enfichable du raccord B jusqu'à ce que

vous l'entendiez s'enclencher.

Installez le système de tube de fixation comme suit:

- Enfoncez le tube de fixation (8) avec l'échelle de 41-75mbars dans le tube de fixation

inamovible (7) en le faisant légèrement tourner.

- Enfoncez maintenant le tube de fixation (9) avec l'échelle de 81-115mbars dans le tube

de fixation (8) en le faisant légèrement tourner.

Ouvrez les soupapes d'arrêt des raccords B, C et D.

En pompant avec la soufflante simple (12), amenez le système à une pression d'essai de

110mbars.

Fermez la soupape d'arrêt du raccord C pour éviter une chute de pression.

Attendez pendant 10 minutes que les températures s'équilibrent, pour donner à l'air amené la

possibilité de se réchauffer ou de se refroidir.

Prolonger le temps d'équilibrage lorsque les modifications de température sont

importantes!

Effectuez le contrôle pendant une durée de 10 minutes. Pendant ce laps de temps la pression

indiquée ne doit pas retomber.

FRANÇAIS 17

5 Service et réalisation de contrôles avec le ROTEST GW 150/4

5.1 Contrôle de résistance des installations domestiques de gaz conformément à

DVGW-TRGI (G600)

Tenir compte des points suivants:

Pour les conduites récemment posées, le contrôle de résistance doit être effectué sans

robinetteries.

Toutes les ouvertures des conduites doivent être fermées de manière étanche avec des

bouchons, des capuchons, des obturateurs ou des brides d'obturation en métal.

Les liaisons avec des conduites de gaz ne sont pas autorisées.

Effectuez le contrôle de résistance avant que les conduites soient sous crépi ou cachées, et

leurs raccords enduits ou gainés.

Si le contrôle doit être effectué à partir d'un raccord pour un compteur monotubulaire de gaz,

la conduite doit être fermée au niveau de la soupape de raccordement, avec le capuchon de

compteur monotubulaire à raccord fileté (22).

Procédez de la manière suivante:

Fermez toutes les soupapes d'arrêt de votre ROTEST GW 150/4.

Enfoncez le tuyau de raccordement (6) sur l'embout enfichable du raccord A jusqu'à ce que

vous l'entendiez s'enclencher.

Placez un bouchon d'essai adapté dans l'extrémité ouverte de la conduite et amenez à

expansion le caoutchouc du bouchon en tournant l'écrou à ailettes, jusqu'à ce que le

bouchon soit bien fermé et étanche.

Installez l'extrémité libre du tuyau de raccordement (6) sur le raccord du bouchon d'essai.

En pompant avec la pompe à main, amenez le système à une pression d'essai de 1 bar.

Attendez pendant 10 minutes que les températures s'équilibrent, pour donner à l'air amené la

possibilité de se réchauffer ou de se refroidir.

En cas de fortes modifications de température ou de pression de l'air, 10 minutes ne

suffisent pas! Le temps d'équilibrage peut durer jusqu'à deux heures en fonction des

modifications de température ou de pression!

Effectuez le contrôle pendant une durée de 10 minutes. Pendant ce laps de temps la pression

indiquée ne doit pas retomber llen.

5.2 Contrôle d'étanchéité des installations domestiques de gaz conformément à

DVGW-TRGI (G600)

Pour des conduites de gaz propane liquéfié avec colonne d'eau jusqu'à 150 mbars

Pour des conduites de gaz liquéfié basse pression avec colonne d'eau 40 jusqu'à 60

mbars

Tenir compte des points suivants:

Le contrôle d'étanchéité s'étend aux conduites et aux robinetteries, à l'exception toutefois des

appareils à gaz et des dispositifs correspondants de régulation et de sécurité.

Le contrôle d'étanchéité doit être effectué avant que les conduites soient sous crépi ou

cachées, et leurs raccords enduits ou gainés.

Le compteur à gaz peut être intégré dans le contrôle d'étanchéité.

Si le contrôle doit être effectué à partir d'un raccord pour un compteur monotubulaire de gaz,

la conduite doit être fermée au niveau de la soupape de raccordement avec le capuchon de

compteur monotubulaire à raccord fileté (22).

18 FRANÇAIS