Safety Note

Output signal

SW5: 0(2)-5(6) V/5(6)-10 V ❺⑥

Output signal from the terminal X can be

used for indication of the current position.

Note:

Range depends on the DIP switch settings.

Prior to assembly and commissioning

This function is available if switch No.4: ---/

to avoid injury of persons and damages

Sequential is set.

Supply voltage

of the devices, it is absolutely necessary

Supply voltage (24V~ -15 to +10 %, 50 Hz)

to carefully read and observe these

SW6: Proportional/3 point ❺⑦

must be connected to the terminals SN

instructions.

Actuator can operate as “simple” 3-point

and SP.

actuator, if the 3-point function is selected.

Necessary assembly, start-up, and

Power supply should be connected on

maintenance work must be performed

SN and SP ports. On port 1 or 3 24 VAC

Dimensions

only by qualied, trained and authorized

signal is connected for rising or lowering

personnel.

of actuator. Return signal X indicates the

Prior to assembly and maintenance work

DIP switch settings

correct position.

on the controller, the system must be:

U I

- depressurized,

2 V_--- V 0 V_--- V

Note:

Direct Inverse

- cooled down,

--- Sequential

If 3 point function is selected actuator does

- emptied and

0(2)_5(6) V 5(6)_10 V

not respond to any control signal on port Y.

Proportional 3 point/RL

- cleaned.

LOG. ow LIN. ow

It only rises and lowers spindle if power is

100 % k

VS

RED. k

VS

supplied on port 1 or 3.

Please comply with the instructions of the

Reset Reset

system manufacturer or system operator.

SW7: LOG. ow/LIN. ow ❺⑧

Factory settings:

Factory setting is:

ALL switches are on OFF position! ❺①

LOG. Flow (characteristic of valve is

Do not remove the cover before the power

unchanged)

Note:

supply is fully switched o.

All combinations of DIP switches are

Note:

allowed. All functions that are selected are

added consecutively. There is only one logic

Large AB-QM valve has linear characteristic.

Disposal instruction

override of functionalities i.e. the switch No.6

With setting switch to LIN ow the

Proportional /3 point, which sets actuator to

characteristic remains linear. With setting

This product should be

ignore control signal and works as a “simple

switch to LOG ow the characteristic of

dismantled and its

3-point actuator

actuator is modied the way that actuator

components sorted, if

and valve work together as valve with LOG

possible, in various groups

SW1: U/I ❺②

characteristic.

before recycling or disposal.

Factory setting:

Always follow the local disposal

SW8: 100 % K

/RED. K

❺⑨

VS

VS

regulations.

Voltage control signal (0-10 V).

Note:

SW2: 2-10 V/0-10 V ❺③

This function works proper only with

Mounting

logarithmic (equal percentage) valves.

Factory setting is:

Fix the AME 85QM on the valve.

2-10 V.

SW9: Reset ❺⑩

Admissible Installation Positions .

After the actuator has been connected

SW3: Direct/Inverse ❺④

to power supply, the actuator will start

the self-adjustment procedure. The

Wiring

Factory setting is:

indicator LED ashes until self adjustment

DIRECT

is nished. The duration depends on the

spindle travel and will normally last a few

SW4: ---/Sequential ❺⑤

minutes. The stroke length of the valve is

Two actuators can be set to work parallel

Do not touch anything on the PCB!

stored in the memory after self adjustment

with one control signal. If the SEQUENTIAL

Switch o the power line before wire the

has been completed. To restart self

is set than an actuator responds to split

actuator! Lethal voltage!

adjustment, change the position of RESET

control signal (see 0(2)-5(6) V/5(6)-10 V).

Wire the actuator according to the wiring

switch (switch No.9). If the supply voltage

diagram.

is switched o or falls below 80 % in more

Note:

than 0.1 s, the current valve position will be

This combination works in combination with

stored in the memory and all data remain

Control signal

switch No.5: 0(2)-5(6)V/5(6)-10 V

saved in the memory also after a power

Control signal from the controller must be

supply cut-out.

connected to terminals Y (input signal) and

SN (common) on the AME printed board.