Xylem e-NSC, e-NSCF, e-NSCC: 7 Troubleshooting
7 Troubleshooting: Xylem e-NSC, e-NSCF, e-NSCC

en - Translation of the original instructions
6.3 Inspection checklist
Cause Remedy
The protective device against
Check the:
Check the coupling Check the flexible elements of the
dry running has tripped.
coupling. Replace the relevant
• liquid level in the tank, or the
parts if there is any sign of wear
mains pressure
and check the alignment.
• protective device and its con-
necting cables
Check the mechanical seal Check for leakage of the mechani-
cal seal. Replace the mechanical
The fuses for the pump or
Replace the fuses.
seal if leakage is found.
auxiliary circuits are blown.
Checking the bearing seals Check correct seating of axial seal
rings mounted on the shaft. Only
7.3 The electric pump starts, but the thermal
gentle contact of the sealing lip
protector trips or the fuses blow immediately
shall be established.
after
6.4 Disassemble and replace the pump parts
Cause Remedy
For more information about spare parts and assembly and disassem-
The power supply cable is
Check the cable and replace as nec-
bly of the pump see Figure 1 , Figure 2 , Figure 3 , or Figure 4 .
damaged.
essary.
See the Repair and Assembly Instructions which are available for
download from our homepage.
The thermal protection or fuses
Check the components and replace
are not suited for the motor
as necessary.
current.
7 Troubleshooting
The electric motor is short cir-
Check the components and replace
cuit.
as necessary.
7.1 Troubleshooting for users
The motor overloads. Check the operating conditions of the
pump and reset the protection.
The main switch is on, but the electric pump does not start.
Cause Remedy
7.4 The electric pump starts, but the thermal
The thermal protector incorpo-
Wait until the pump has cooled
protector trips or the fuses blow a short time
rated in the pump (if any) has
down. The thermal protector will au-
after
tripped.
tomatically reset.
The protective device against
Check the liquid level in the tank, or
Cause
Remedy
dry running has tripped.
the mains pressure.
The electrical panel is situated in an
Protect the electrical panel from
excessively heated area or is ex-
heat source and direct sunlight.
The electric pump starts, but the thermal protection trips a varying time
posed to direct sunlight.
after.
The power supply voltage is not
Check the operating conditions
within the working limits of the mo-
of the motor.
Cause
Remedy
tor.
There are foreign objects (solids or
Contact the Sales and Service
A power phase is missing. Check the
fibrous substances) inside the
Department.
pump which have jammed the im-
• power supply
peller.
• electrical connection
The pump is overloaded because
Check the actual power require-
it is pumping liquid that is too
ments based on the characteris-
7.5 The electric pump starts, but the thermal
dense and viscous.
tics of the pumped liquid and then
protector trips a varying time after
contact the Sales and Service
Department.
Cause
Remedy
The pump runs but delivers too little or no liquid.
There are foreign objects (sol-
Contact the local sales and service
ids or fibrous substances) in-
representative.
side the pump which have jam-
Cause
Remedy
med the impeller.
The pump is clogged. Contact the Sales and Service Department.
The pumps delivery rate is
Partially close the on-off valve down
higher than the limits specified
stream until the delivery rate is equal
The troubleshooting instructions in the tables below are for installers
on the data plate.
or less than the limits specified on
only.
the data plate.
7.2 The main switch is on, but the electric
The pump is overloaded be-
Check the actual power requirements
cause it is pumping liquid that
based on the characteristics of the
pump does not start
is too dense and viscous.
pumped liquid and replace the motor
accordingly.
Cause
Remedy
The motor bearings are worn. Contact the local sales and service
There is no power supply. • Restore the power supply.
representative.
• Make sure all electrical connec-
tions to the power supply are in-
tact.
7.6 The electric pump starts, but the system's
general protection is activated
The thermal protector incorpo-
Wait until the pump has cooled down.
rated in the pump (if any) has
The thermal protector will automati-
tripped.
cally reset.
Cause
Remedy
The thermal relay or motor
Reset the thermal protection.
A short circuit in the electrical system. Check the electrical system.
protector in the electric control
panel has tripped.
e-NSC Installation, Operation, and Maintenance Manual 19

en - Translation of the original instructions
7.7 The electric pump starts, but the system's
Cause Remedy
residual current device (RCD) is activated
The motor bear-
Contact the local sales and service representa-
ings are worn.
tive.
Cause Remedy
There are foreign
Contact the local sales and service representa-
There is an ground
Check the insulation of the electrical system
objects inside the
tive.
(earth) leakage.
components.
pump.
7.8 The pump runs but delivers too little or no
For any other situation, refer to the local sales and service representa-
tive.
liquid
Cause Remedy
There is air inside the
• Bleed the air
pump or the piping.
The pump is not correctly
Stop the pump and repeat the prime pro-
primed.
cedure.
If the problem continues:
• Check that the mechanical seal is
not leaking.
• Check the suction pipe for perfect
tightness.
• Replace any valves that are leaking.
The throttling on the deliv-
Open the valve.
ery side is too extensive.
Valves are locked in closed
Disassemble and clean the valves.
or partially closed position.
The pump is clogged. Contact the local sales and service repre-
sentative.
The piping is clogged. Check and clean the pipes.
The rotation direction of
Change the position of two of the phases
the impeller is wrong
on the terminal board of the motor or in
(three-phase version)
the electric control panel.
.
The suction lift is too high
Check the operating conditions of the
or the flow resistance in
pump. If necessary, do the following:
the suction pipes is too
• Decrease the suction lift
great.
• Increase the diameter of the suction
pipe
7.9 The electric pump stops, and then rotates
in the wrong direction
Cause
Remedy
There is a leakage in one or both of the follow-
Repair or replace the
ing components:
faulty component.
• The suction pipe
• The foot valve or the check valve
There is air in the suction pipe. Bleed the air.
7.10 The pump starts up too frequently
Cause
Remedy
There is a leakage in one or both of the fol-
Repair or replace the
lowing components:
faulty component.
• The suction pipe
• The foot valve or the check valve
There is a ruptured membrane or no air
See the relevant instruc-
pre-charge in the pressure tank.
tions in the pressure
tank manual.
7.11 The pump vibrates and generates too
much noise
Cause
Remedy
Pump cavitation Reduce the required flow rate by partially closing
the on-off valve downstream from the pump. If the
problem persists check the operating conditions of
the pump (for example height difference, flow re-
sistance, liquid temperature).
20 e-NSC Installation, Operation, and Maintenance Manual
Оглавление
- 1 Introduzione e sicurezza
- 2 Movimentazione e stoccaggio
- 4 Installazione
- 5 Messa in funzione, avvio,
- 7 Risoluzione dei problemi
- 1 Introduction and Safety
- 2 Transportation and Storage
- 4 Installation
- 5 Commissioning, Startup,
- 7 Troubleshooting
- 1 Introduction et sécurité
- 2 Transport et stockage
- 4 Installation
- 5 Contrôle de réception, Démarrage, Fonctionnement et Extinction
- 7 Recherche des pannes
- 1 Einführung und Sicherheit
- 2 Transport- und Lagerung
- 4 Montage
- 5 Inbetriebnahme, Anfahren,
- 7 Fehlerbehebung 6 Wartung
- 1 Giriş ve Güvenlik
- 2 Taşıma ve Depolama
- 4 Montaj
- 5 Devreye alma, Başlatma,
- 7 Sorun Giderme
- 1 Подготовка и техника
- 2 Транспортирование и
- 4 Установка
- 5 Ввод в эксплуатацию, запуск,
- 6 Техническое обслуживание