Dimplex SRX 160C: Hydraulic connection

Hydraulic connection: Dimplex SRX 160C

background image

- 2 - 

Hydraulic connection 

To ensure a sufficient water flow rate through the fan convec-

tors, observe the following points: 

-

The  devices  are  not  suitable  for  installation  in  single-pipe 

systems. 

-

The  nominal  width  of  the  connection  pipe  must  have  a 

minimum diameter of 15 mm. 

-

If the devices are installed in a heating system with various 

heat  distribution  systems  (e.g.  underfloor  heating),  a  sepa-

rate circuit is required to guarantee a sufficient water  flow 

rate. 

-

For optimum operation (heat output) of the fan convectors, 

a hydraulic balance is required on the heating system.  

Fig.  5  shows  the  various  hydraulic  connection  options  on  the 

device.  The  recommended  flow  and  return  connections  are 

shown in fig. 5 and fig. 4. The  heating pipes can be laid in the 

floor or in the wall. The device is supplied with two copper pipes 

with a diameter of 15 mm that are fitted on the heat exchanger 

at the factory.  

Before and during filling of the heating system, all pipe connec-

tions must be checked for leaks. During filling, the bleeder valve 

(see fig. 4) must be open such that air can escape from the de-

vice. If necessary, bleed again following commissioning (circulat-

ing pump running). 

Connect the condensate pipe supplied to the outlet nozzle and 

route to a suitable outlet with a gradient of at least 5°. 

Electrical connection 

WARNING – The device must be grounded! 

WARNING  –  Phase  conductor  (brown)  and  neutral  conductor 

(blue)  must  not  be  swapped  as  this  may  cause  malfunctions. 

The electrical connection should have a supply voltage of ~230-

240V, 50 Hz. 

The device must be installed by a qualified electrician in compli-

ance  with  the  existing  standards  and  local  installation  guide-

lines. 

Before performing installation, ensure that the power supply is 

switched off.  

The device is equipped with a flexible 1 m connection cable (4 x 

0.75 mm²), which can be used to connect the heater directly to 

the power supply via a suitable wall socket.  

In  the  electrical  supply  line,  fit  a  circuit  breaker  for  each  pole 

with a contact opening width of at least 3 mm. Automatic fuses 

are also permitted as separators. Automatic fuses should have a 

delayed tripping characteristic. 

Conductor configuration of the connection cable: 

Brown: 'L' – supply voltage phase conductor 

Blue: 'N' – supply voltage neutral conductor 

Green/yellow: 'PE' – grounding conductor 

Black: control conductor (temperature reduction; on/off) 

For circuit diagram, see fig. 6.1 resp. fig. 6.2. 

Control conductor 

By  activating  the  control  conductor,  see  fig.  6.1,  the  set  tem-

perature  on  the  device  is  lowered  or  raised  depending  on  the 

selected mode. 

See also "Changing automatically the set temperature" 

The  temperature  change  is  forwarded  to  any downstream  de-

vices via the control conductor. 

If  a  programming  cassette  is  used,  the  control  signal  from  the 

cassette, which is plugged into the pilot device, is forwarded to 

any downstream devices; see fig. 6.2. 

The  control  conductor  does  not  have  to  be  in  phase  with  the 

supply connection. If the control conductor is not used, it must 

be properly insulated. 

WARNING  –  if  you  switch  over  to  controlled  operation,  the 

mains voltage is on this conductor! 

WARNING – do not ground the control conductor. 

When taking out of service, e.g. for maintenance work, ensure 

that both the mains supply and the control conductor are dis-

connected  from  the  power  supply,  because  this  may  result  in 

external  voltage  (via  a  timer  contact  or  pilot  device  with  pro-

gramming cassette). 

Final installation 

Fit casing cover following completion of installation work. To do 

this, screw in the four fixing screws on the underside of the de-

vice, see fig. 2.  

Operation 

The control panel is shown in fig. 3.  

The individual elements have the following meaning: 

A  –   Operating mode button 

B  –   On/off indicator 

C  –   Cooling mode indicator 

D  –  Heating mode indicator 

E  –  Fan level button 

F  –  Low fan level indicator 

G  –  Medium fan level indicator 

H  –  High fan level indicator 

J  –  Thermostat setting wheel 

K  –   Cover for programming cassette slot 

Heating mode 

Press the 

 button once or several times until the red   in-

dicator lights up. 

Set  the  desired  room  temperature  with  the  setting  wheel. 

Depending  on  the  current  room  temperature  and  the  tem-

perature  set  on  the  thermostat,  the  electronics  calculate 

which fan level (fan speed) to use.  

There are 3 possible fan levels. If necessary, the number of pos-

sible fan levels can be reduced. For  instance,  to  limit  the  fan 

levels to a maximum of 2, press the 

 button once or sev-

eral times until the red 

2

 indicator lights up.