De Dietrich MS 24 BIC – страница 4

Инструкция к Настенному Котлу De Dietrich MS 24 BIC

3. COMMISSIONING THE BOILER

To light the boiler correctly, proceed as follows:

1) power the boiler

2) open the gas tap;

3) press the button (

) and switch the boiler to Summer ( ), Winter ( ) or heating only ( );

4) press the heating circuit (+/-) and domestic hot water circuit ( ) temperature adjustment buttons ( ) in order to ignite

the main burner.

When the boiler is lit, the symbol ( ) will appear on the display.

In the Summer position ( ) the main burner will only ignite if a DHW tap is opened.

WARNING

During initial ignition, the burner may not ignite (causing the boiler to shut down) until any air in the gas pipes is vented. In

this case, repeat the ignition procedure until gas reaches the burner. Press button (

), for at least 2 seconds.

0805_2302 / CG_2072

SYMBOL KEY

BUTTON KEY

Operation in the heating mode

On / Off / Summer / Winter / heating only

Flame present (burner on)

(

+/-) : CH temperature adjustment

No ame (ignition failure)

(

+/-) : DHW temperature adjustment

Operation in the DHW mode

Reset

Generic fault

Information

RESET

No water (Low system pressure)

Numerical signal (Temperature, fault code, etc.)

Figure 1

OPERATING INSTRUCTIONS

71.06199.02 - EN

61

4. ADJUSTING ROOM TEMPERATURE AND DHW TEMPERATURE

The system must be tted with a room thermostat for controlling indoor temperature.

Adjust the room temperature (

) and the DHW temperature ( ) by pressing the respective +/- (gure 1). The ignition

of the burner is shown on the display with the symbol (

) as described in section 3.

HEATING

While the boiler is operating in the heating mode, the display (gure 1) shows the ashing symbol (

) and the heating

delivery temperature (°C).

DOMESTIC HOT WATER

While the boiler is operating in the DHW mode, the display (gure 1) shows the ashing symbol ( ) and the DHW output

temperature (°C).

5. DESCRIPTION OF BUTTON (Summer - Winter - Heating only - Off)

Press this button to set the following operating modes:

• SUMMER

• WINTER

• HEATING ONLY

• OFF

In the SUMMER mode, the display shows (

). The boiler satises requests for DHW only while central heating is NOT

enabled (ambient frost protection function active).

In the WINTER mode, the display shows (

). The boiler satises requests for both DHW and central heating (am-

bient frost protection function active).

In the HEATING ONLY mode, the display shows ( ). The boiler satises requests for central heating only (ambient frost

protection function active).

In the OFF mode, the display shows neither of the above two symbols (

) ( ). In this mode, only the ambient frost

protection function is active while requests for DHW and central heating are not satised.

6. FILLING THE SYSTEM

WARNING

Disconnect the boiler from the mains power supply using the two-pole switch.

IMPORTANT: Regularly check that the pressure displayed on the pressure gauge is 0.7 - 1.5 bar, with the boiler cold.

In case of overpressure, open the boiler drain tap. In case of insufcient temperature, open the boiler lling tap (gure 3).

Open the tap very slowly in order to vent the air.

OPERATING INSTRUCTIONS

71.06199.02 - EN

62

A: System emptying tap

B: Boiler emptying tap

C: System lling tap

D: Pressure gauge

Figure 2

The boiler is tted with a hydraulic pressure gauge which prevents the boiler from working if there is no water.

N.B.: In case pressure drops occur frequently, have the boiler checked by an authorised Service Engineer.

7. TURNING OFF THE BOILER

To turn off the boiler, disconnect the electric power supply. In “OFF” mode (section 5) the boiler remains off (the display

indicates OFF) though the electrical circuits remain live and the frost protection device is enabled (section 9).

8. GAS CONVERSION

The boilers can operate both on natural gas and LPG.

All gas conversions must be made by an authorised Service Engineer.

9. PROLONGED SHUTDOWN. FROST PROTECTION

Do not drain the whole system as lling up with water again causes unnecessary and harmful scale to build up inside the

boiler and the heating elements. If the boiler is not used during winter and is therefore exposed to the danger of frost, add

some specic anti-freeze to the water in the system (e.g.: propylene glycol coupled with corrosion and scale inhibitors).

The electronic boiler management system includes a “frost protection” function for the heating system which, when delivery

temperature falls below 5°C, operates the burner until a delivery temperature of 30°C is reached.

The frost protection function is enabled if:

* the boiler is electrically powered;

* the gas tap is open;

* the system is at the correct pressure;

* the boiler is not blocked.

OPERATING INSTRUCTIONS

71.06199.02 - EN

63

10. TROUBLESHOOTING

Faults are shown on the display with an error code (e.g.: E 01):

To RESET the boiler, press and hold down “R” for at

least 2 seconds. If this fault persists, call the Authorised

Service Centre.

0607_1205

N.B.: 5 reset attempts can be performed after which

the boiler shuts down. To reset again, switch off the

boiler for a few seconds.

RESETTABLE

faults

Figure 3

CODE

FAULT CORRECTIVE ACTION

DISPLAYED

Press and hold down “R” for at least 2 seconds. If this fault persists, call the

E01 Failed ignition shutdown

Authorised Service Centre.

Press and hold down “R” for at least 2 seconds. If this fault persists, call the

E02 Safety thermostat tripped

Authorised Service Centre.

Flue thermostat/ ue pressure

E03

Call the Authorised Service Centre.

switch tripped

Shutdown after 6 consecutive

Press and hold down “R” for at least 2 seconds. If this fault persists, call the

E04

ame losses

Authorised Service Centre.

E05 Flow sensor failure Call the Authorised Service Centre.

E06 DHW sensor fault Call the Authorised Service Centre.

Hydraulic pressure switch

Check that the pressure in the system is correct; See section 6. If this fault

E10

block

persists, call the Authorised Service Centre.

Probable blocked pump safety

E25/E26

Call the Authorised Service Centre.

trip

Press and hold down “R” for at least 2 seconds. If this fault persists, call the

E35 Parasite ame (ame error)

Authorised Service Centre.

Switching off due to reductions

E96

RESET is automatic. If this fault persists, call the Authorised Service Centre

in power supply

N.B.: in case of a fault, the display backlighting ashes together with the error code.

11. ROUTINE MAINTENANCE INSTRUCTIONS

To keep the boiler efcient and safe, have it checked by the authorised Service Centre at the end of every operating period.

Careful servicing ensures economical operation of the system.

Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily ammable cleaners (e.g.: petrol,

alcohol, and so on). Always switch off the appliance before cleaning it (see section 7 Switching off the boiler).

OPERATING INSTRUCTIONS

71.06199.02 - EN

64

12. GENERAL INFORMATION

The following notes and instructions are addressed to tters to allow them to carry out trouble-free installation. Instructions

for igniting and using the boiler are contained in the ‘Instructions for Users’ section.

This boiler can be connected to any type of double- or single-pipe convector plate, radiator or thermoconvector. Design

the system sections as usual, though, bearing in mind the available ow-head at the plate, as shown in section 25.

Do not leave any packaging (plastic bags, polystyrene, etc.) within reach of children, as it is a potential source of danger.

Initial lighting of the boiler must be carried out by an authorised Service Engineer, as indicated on the attached sheet.

Failure to observe the above will render the guarantee null and void.

ADDITIONAL PUMP WARNING

If an additional pump is used on the heating system, position it on the boiler return circuit. This will allow the correct

operation of the water pressure switch.

SOLAR WARNING

if the instantaneous (mixed) boiler is connected to a system with solar panels, the maximum temperature of the domestic

hot water entering the boiler must not exceed 60°C.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

65

13. INSTRUCTIONS PRIOR TO INSTALLATION

This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure.

It must be connected to a central heating system and to a domestic hot water supply system according to its performance

and power output.

Do the following before connecting the boiler:

a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings

on the packaging and the rating plate on the appliance.

b) Make sure that the ue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gases

from other appliances are expelled through the same ue duct, unless the latter has been specially designed to collect

exhaust gas from more than one appliance, in compliance with current laws and regulations.

c) Make sure that, if the boiler is connected to existing ue ducts, these have been thoroughly cleaned as residual products

of combustion may detach from the walls during operation and obstruct the ow of fumes.

To ensure correct operation and maintain the warranty, observe the following precautions:

1. DHW circuit:

1.1. If the water is harder than 20 °F (1 °F = 10 mg calcium carbonate per litre of water), install a polyphosphate dispenser

or an equivalent treatment system, compliant with current regulations.

1.2. Thoroughly ush the system after installation of the appliance and before use.

1.3. The materials used for the product’s DHW circuit comply with Directive 98/83/CE.

2. Heating circuit

2.1. new system

Before proceeding with installation of the boiler, the system must be cleaned and ushed to eliminate residual

thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, plastic

and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products are:

SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliance

with the manufacturers’ instructions.

2.2. existing system:

Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable

proprietary products as described in section 2.1.

To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such

as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with the

manufacturers’ instructions.

Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.

overheating and excessive noise of the heat exchanger).

Failure to observe the above will render the warranty null and void.

13. INSTALLAZIONE DELLA CALDAIA 14. INSTALLING THE BOILER

After deciding the exact location of the boiler, make sure there is sufcient room to perform maintenance operations (at

least 450 mm of headroom is required in order to replace the expansion vessel).

Connect the system to the gas and water inlets present on the lower bar of the template. Fit two G3/4 taps (ow and

return) on the central heating circuit; these taps make it possible to carry out important operations on the system without

draining it completely. If you are either installing the boiler on an existing system or replacing one, as well as the above,

t a settling tank under the boiler on the system return line in order to collect any deposits and scale circulating in the

system after ushing. After xing the boiler to the template, connect the ue and air ducts, supplied as accessories, as

described in the following sections.

If the model

24 BIC

natural draught boiler is installed, connected it to the ue with a metal pipe resistant to normal me-

chanical stress, heat, products of combustion and relative condensate.

IMPORTANT

After lling the boiler, vent the entire internal circuit and the system as follows:

close the gas on-off valve;

power the boiler.

open the vent valve on the pump body;

press ( ) to set the boiler in the “WINTER” operating mode;

send a heat demand from the room thermostat;

open a hot water tap to alternate CH demand with DHW demand;

after a few ignition attempts the boiler will shut down (error E01 appears on the display);

to rest, press and hold down “R” for at least 2 seconds;

repeat the procedure at least another two times;

close the vent valve.

After venting the boiler circuit, proceed with initial lighting.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

66

EXPANSION VESSEL

The boiler features a standard 7.5-litre expansion vessel with a pre-charge pressure of 1 bar. The maximum volume of water in

the system is calculated according to hydrostatic pressure at an average water temperature of 80°C (ow: 95°C return: 75°C).

Hydrostatic pressure (m) 5 6 7 8 9 10

Maximum system volume (l) 138 131 119 107 97 87

Figure 4

WARNING

Tighten the boiler nipple water connections with care (maximum tightening torque 30 Nm).

G”3/4 HEATING FLOW G”1/2 DOMESTIC HOT WATER OUTLET

G”3/4 HEATING RETURN G”1/2 DOMESTIC COLD WATER INLET

G”3/4 GAS INLET TO BOILER

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

67

14. DIMENSIONI CALDAIA 15. DIMENSIONS OF BOILER

24 BIC FF 24 BIC

CG_1848 / 1104_0702

CG_1848 / 1104_0703

Figure 5

16. INSTALLING THE FLUE AND AIR DUCTS

Model 24 BIC FF

The boiler is easy and exible to install thanks to the extensive range of available

accessories, as described below.

The boiler has been designed for connection to a vertical or horizontal coaxial

ue-air duct. A splitting kit is also available if separate ducts are required.

Only accessories supplied by the manufacturer must be used for installation!

WARNING: To optimise operating safety, make sure the flue ducts are firmly

fixed to the wall with suitable brackets.

… COAXIAL FLUE-AIR DUCT (CONCENTRIC)

This type of duct is used to discharge exhaust fumes and draw combustion air

both outside the building and if a LAS ue is tted.

The 90° coaxial curve allows the boiler to be connected to a ue-air duct in any

direction as it can be rotated by 360°. It can also be used as a supplementary

curve combined with a coaxial duct or a 45° curve.

Figure 6

If fumes are discharged outside the building, the ue-air duct must protrude

at least 18 mm from the wall to allow an aluminium weathering surround to be

tted and sealed to avoid water inltrations.

Make sure there is a minimum upward slope towards the outside of 1 cm per

metre of duct.

0805_2901 / CG_2073

A 90° curve reduces total duct length by 1 metre.

A 45° curve reduces total duct length by 0.5 metres.

Connector

The first 90° curve is not considered when calculating the maximum avai-

lable length.

Figure 7

Use of DIAPHRAGM

Boiler model Length (m)

on INLET LINE A

0,5 73

24 BIC FF

0,5 ÷ 2 80

2 ÷ 4 No

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

68

16.1 HORIZONTAL FLUE INSTALLATION EXAMPLES

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)

0512_2001

L max = 3 m (Ø 60/100 mm)

L max = 3 m (Ø 60/100 mm)

7 m (Ø 80/125 mm)

7 m (Ø 80/125 mm)

16.2 LAS FLUE DUCT INSTALLATION EXAMPLES C42 TYPE

0503_0907/CG1640

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)

16.3 VERTICAL FLUE INSTALLATION EXAMPLES

This type of installation can be carried out on either a at or a pitched roof by tting a ue terminal and a special weathering

surround with sleeve (both available on request).

0503_0908/CG1641

L max = 10 m (Ø 80/125 mm)

L max = 8 m (Ø 80/125 mm)

L max = 9 m (Ø 80/125 mm)

For detailed installation instructions, consult the technical data provided with the accessories.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

69

… SEPARATE FLUE AND AIR DUCTS

This type of installation makes it possible to discharge exhaust fumes both outside the building and into single ue ducts.

Comburent air can be drawn in at a different location from that of the ue terminal. The splitting kit comprises a ue duct

adaptor (100/80) and an air duct adaptor. For the air duct adaptor, t the screws and seals previously removed from the cap.

Position

CO

%

2

Boiler model (L1+L2)

of air regulator

G20 G31

0 ÷ 20 1

24 BIC FF

6,1 8,7

20 ÷ 30 2

The first 90° curve is not considered when calculating the maximum available length.

The 90° curve allows the boiler to be connected to a ue-air duct in any direction as it can be rotated by 360°. It can also

be used as a supplementary curve combined with a duct or a 45° curve.

A 90° curve reduces total duct length by 0.5 metres.

• A 45° curve reduces total duct length by 0.25 metres.

Adjusting the air regulator for separate flues

This regulator must be adjusted to optimise combustion efciency and parameters.

After turning the air intake connecter, which can be mounted both to the right and the left of the exhaust ue duct, suitably

adjust the excess air according to the total length of the combustion exhaust and inlet ue ducts.

Turn this regulator anticlockwise to decrease the excess of comburent air and vice-versa to increase it.

To ne tune, use a combustion product analyser to measure the amount of CO

in the fumes at maximum heat capacity,

2

and, if a lower value is measured, gradually adjust the air regulator until the amount of CO

indicated in the following table

2

is measured.

To mount this device correctly, consult the relative instructions.

connector

CG_1145 / 1104_0801

aperture

index

Figure 8

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

70

16.4 DIMENSIONS OF SEPARATE OUTLETS

CG_2344 / 1103_3002

16.5 HORIZONTAL SEPARATE FLUE INSTALLATION EXAMPLES - C82

IMPORTANT -

Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.

In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.

1010_0102/CG1643

CG_1643_FR / 1010_0101

L max = 10 m

(L1 + L2) max = 30 m

N.B.: For the C52 type, do not t the ue and air duct terminals on opposite walls of the building.

The inlet ue must have a maximum length of 10 metres for C52 fumes outlets.

If the discharge duct is longer than 6 metres, install the condensate collection kit, supplied as an accessory, near the boiler

IMPORTANT:

if tting a single ue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct

passes through building walls. For detailed installation instructions, consult the technical data provided with the accessories.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

71

17. ELECTRICAL CONNECTIONS

This machine is only electrically safe if it is correctly connected to an efcient earth system in compliance with current

safety regulations.

Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct

LIVE-NEUTRAL polarity.

Use a double-pole switch with a contact separation of at least 3 mm. When replacing the power supply cable, t a

2

harmonised HAR H05 VV-F’ 3x0.75mm

cable with a maximum diameter of 8 mm.

…Access to the power supply terminal block

disconnect the boiler from the mains power supply using the two-pole switch;

remove the two screws xing the control panel to the boiler;

rotate the control panel;

remove the cover and access the wiring area (gure 9).

The 2A fast-blowing fuse is incorporated in the power supply terminal block (to check and/or replace the fuse, pull out

the black fuse carrier).

IMPORTANT: respect polarity L (LIVE) -N (NEUTRAL).

(L) = Live (brown)

(N) = Neutral (blue)

= Earth (yellow-green)

(1) (2) = Contact for room thermostat

CG_1853 / 1103_2302

Figure 9

18. CONNECTING THE ROOM THERMOSTAT

Access the power supply terminal block (gure 9) as described in the previous section;

remove the jumper on terminals (1) and (2);

thread the two-wire cable through the grommet and connect it to these two terminals.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

72

19. GAS CONVERSION

The authorised Technical Assistance Service can convert this boiler to natural gas (G. 20) or liquid gas (G.31).

Carry out the following operations:

A) replace the nozzles of the main burner and the gas diaphragm (if tted);

B) new max. and min. calibration of the pressure regulator.

A) Replace the burner nozzles

carefully pull the main burner off its seat;

replace the main burner nozzles making sure to fully tighten them to prevent gas leaks. Nozzle diameters are specied

in table 2.

replace the gas membrane located on the gas valve (gure 10). The diameter of the membrane is specied in table 2.

Attention: it is not necessary to change parameter F02.

B) Calibrate the pressure regulator

connect the positive pressure test point of a differential pressure gauge (possibly water-operated) to the gas valve

pressure test point (Pb) (Figure 10). Only for models with sealed chambers, connect the negative pressure test point of

the manometer to a “T” tting in order to join the boiler adjustment outlet, the gas valve adjusting outlet (Pc) and the

pressure gauge. (The same measurement can be made by connecting the pressure gauge to the pressure test point

(Pb) after removing the front panel of the sealed chamber);

Measuring burner pressure using methods other than those described could lead to incorrect results as the low pressure

created by the fan in the sealed chamber would not be taken into account.

B1) Adjustment to nominal heat output:

open the gas tap and switch the boiler to the Winter mode;

take the boiler to maximum power as described in section 19.1;

remove the modulator cover;

adjust the tube brass screw (a) until the pressure values shown in table 1 are obtained;

make sure that the dynamic inlet pressure of the boiler, measured at the gas valve pressure test point (Pa) (Figure 10)

is correct (37 mbar for propane or 20 mbar for natural gas).

B2) Adjustment to reduced heat output:

disconnect the modulator power cable and unscrew the screw (b) until a pressure value corresponding to reduced heat

output is achieved (see tab. 1);

reconnect the cable;

mount the modulator cover and seal.

B3) Final checks

attach the additional plate supplied with the transformer, specifying the type of gas and the calibration performed.

gas valve

mod. SIGMA 845

a

0605_1502

CG_2347 / 1104_0406

gas diaphragm

Figure 10

b

Figure 11

ATTENTION

If the natural gas inlet pressure is too low (less than 17 mbar) remove the gas diaphragm installed over the gas valve (g.

10) and set parameter F02=00 on the electronic board (§21).

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

73

19.1 GAS VALVE CALIBRATION FUNCTION

To simplify calibration of the gas valve, the calibration function may be set directly

on the boiler control panel as follows:

a)

hold down the buttons and together for at least 6 seconds;

b) after about 6 seconds, the symbols ash;

c) the display shows, at intervals of one second, “100” and the flow temperature.

0805_2302 / 1002_1201

In this phase, the boiler works at the maximum heating output (100%).

d) press +/- to immediately set the power of the boiler (100% or 0%);

e) adjust the “Pmax/Pmin” screw (gure 10) to set the burner pressure value as

described in table 1.

To adjust pressure at maximum power, turn the “Pmax” screw (g. 10) clockwise

to increase or anti-clockwise to decrease pressure at the burner.

To adjust pressure at minimum power, turn the “Pmin” screw (g. 10) clockwise

to increase or anti-clockwise to decrease pressure at the burner.

f)

press +/- to gradually set the desired power level (interval = 1%).

Press the button to leave the function.

Note:

The function is automatically deactivated after a period of 15 minutes, at the end of which the electronic board returns to

its operating status prior to the activation of the function or prior to reaching the set maximum temperature.

Table of burner nozzles

24 BIC FF 24 BIC

gas type G20 G31 G20 G31

diameter of nozzles (mm) 1,18 0,69 1,18 0,69

Burner pressure (mbar*)

1,7 6,9 1,6 6,6

REDUCED HEAT OUTPUT

Burner pressure (mbar*)

7,8 24,7 7,5 18,1

RATED HEAT OUTPUT

Diameter of gas diaphragm (mm) 4,2 3,5 4,2 3,5

N° nozzles 18

Table 1

Consumption 15°C-1013 mbar

24 BIC FF - 24 BIC

G20 G31

3

Rated power

2,73 m

/h 2,00 kg/h

3

Reduced power

1,26 m

/h 0,92 kg/h

3

p.c.i.

34,02 MJ/m

46,34 MJ/kg

Table 2

* 1 mbar = 10,197 mmH

O

2

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

74

20. VISUALISATION OF PARAMETERS ON THE DISPLAY (“INFO” FUNCTION)

Press “i” for at least 5 seconds to visualise certain boiler information on the display on the front panel of the boiler.

N.B: when the “INFO” function is enabled, the message “A00”, alternating with the boiler delivery temperature,

is shown on the display (figure 12):

0605_2204 / CG_1808

Figure 12

Press buttons (+/-) to display the following information:

A00: current DHW temperature (°C);

A01: current external temperature (°C) (with external sensor connected);

A02: modulation current value (100% = 310 mA);

A03: power range (%) (MAX R);

A04: heating setpoint temperature (°C) - - If the external sensor is connected, the value of the “kt” curve is displayed

(section 26);

A05: current heating delivery temperature (°C);

A06: DHW temperature setpoint (°C);

A07: — — ;

A08: value (l/minx10) of the DHW ow rate;

A09: last error that occurred in the boiler.

This function remains active for 3 minutes. It is possible to interrupt the “INFO” function in advance by pressing button

(i) for at least 5 seconds, or turning off the power to the boiler.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

75

21. PARAMETER SETTINGS

To set the boiler parameters, press ( ) and ( ) together and hold down for at least 6 seconds. When the function is

activate, the “F01” appears on the display alternating with the value of the parameter shown.

Edit parameters

Press (+/– ) to scroll through the parameters;

Press (+/– ) to edit each parameter;

Press ( ), to save the changes. “MEM” appears on the display;

Press (i), to exit without saving. “ESC” appears on the display.

Factory settings

Description of parameters

24 BIC FF 24 BIC

Type of boiler

F01

10 20

10 = sealed chamber 20 = atmospheric chamber

Gas used

00 = METHANE

F02

02

01 = LPG

02 = METHANE (WITH DIAPHRAGM)

F03

Hydraulic system 15

Setting programmable relay 1 (See SERVICE instructions)

00 = no associated function

01 = condominium alarm

F04

02 = ambient fan

04

03 = not used

04 = zone pump controlled by room thermostat (230V)

05 = not used

F05

Setting programmable relay 2 (

DHW pump

)

03

Maximum CH setpoint (°C)

F06

00

00 = 85°C - 01 = 45°C (function unavailable)

F07

DHW inlet priority conguration

00

F08

CH max. output (0-100%)

100

F09

DHW max. output (0-100%)

100

F10

Min. heating output (0-100%)

00

Delay prior to new ignition in CH mode

F11

03

(00-10 minutes) - 00=10 seconds

F12

Diagnostics (See SERVICE Instructions)

--

F13-F14-F15

Factory settings (no change) 00

Anti-legionella function

F16

00 = disabled

00

55...67 = enabled (setpoint °C)

CH pressure sensor selection

F17

00 = hydraulic pressure sensor

00

01 = hydraulic differential pressure sensor

F18

Manufacture information

00

22. ADJUSTMENT AND SAFETY DEVICES

The boiler has been designed in full compliance with European reference standards and in particular is tted with the

following:

Air pressure switch (model 24 BIC FF)

This device only allows the burner to ignite if the exhaust ue duct is in perfect working order.

In the event of one or more of the following faults:

ue terminal obstructed

venturi tubes obstructed

fan blocked

venturi tube connection - pressure switch tripped

the boiler remains on standby and error code E03 is displayed (see table in section 10).

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

76

Fumes thermostat (model 24 BIC)

This device has a sensor positioned on the left section of the fumes hood and shuts off the gas ow to the main burner

if the ue is obstructed and/or if there is no draught.

In these conditions the boiler shuts down and displays error code E03 (section 10).

After eliminating the problem, press button ( ), for at least 2 seconds to re-ignite immediately.

It is forbidden to disable this safety device

Safety thermostat

Thanks to a sensor placed on the CH ow line, this thermostat interrupts the ow of gas to the burner if the water in

the primary circuit overheats. In these conditions, the boiler is blocked and only after the fault has been eliminated can

it be ignited again by pressing ( ), for at least 2 seconds.

It is forbidden to disenable this safety device

Flame ionization detector

The ame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas

failure or incomplete ignition of the burner.

In these conditions, the boiler is blocked after 3 ignition attempts.

Press ( ), for at least 2 seconds to re-establish normal operating conditions.

Hydraulic pressure switch

This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.

Pump overrun for heating circuit

The electronically-controlled pump post-circulation function lasts 180 seconds and is enabled, in the heating mode, if

the ambient thermostat causes the burner to go out.

Pump overrun for DHW circuit

The electronically-controlled pump post-circulation function lasts 30 seconds and is enabled, in the DHW mode, if the

probe causes the burner to go out.

Frost protection device (CH and DHW systems)

The electronic boiler management system includes a “frost protection” function for the heating system which, when

delivery temperature falls below 5°C, operates the burner until a delivery temperature of 30°C is reached.

This function is enabled when the boiler is switched on, the gas supply is open and the system is correctly pressurised.

Water not circulating in primary circuit (pump probably blocked)

If there is insufcient or no water circulating in the primary circuit, the boiler blocks and the error code E25 is shown on

the display (section 10).

Anti-block pump function

If no heat demand is received for 24 consecutive hours, in the heating mode, the pump will automatically start and

operate for 10 seconds. This function is operative when the boiler is powered.

• Three-way valve anti-blockage function

If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This

function is operative when the boiler is powered.

Hydraulic safety valve (heating circuit)

This device is set to 3 bar and is used for the heating circuit

.

Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.

N.B.: domestic hot water is guaranteed even if the NTC sensor develops a fault. In this case, temperature is controlled

by the delivery sensor.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

77

23. POSITIONING THE IGNITION AND FLAME-SENSING ELECTRODE

9912070100

Figure 13

24. CHECKING COMBUSTION PARAMETERS

To measure combustion efciency and the toxicity of the products of combustion, the boiler is tted with two dedicated

test points.

One connection point is connected to the exhaust duct and is used to measure combustion efciency and the toxicity of

the products of combustion.

The other is connected to the air intake circuit and is used to check for the presence of any products of combustion

circu¬lating in installations with co-axial ues.

The following parameters can be measured using the test point connected to the exhaust duct:

temperature of the products of combustion;

concentration of oxygen (O

) or, alternatively, carbon dioxide (CO

);

2

2

concentration of carbon monoxide (CO).

The temperature of the comburent air must be measured on the test point located on the air intake ue by inserting the

measurement sensor by about 3 cm.

N.B.: to regulate the rated power, see chapter 19 (B1)

For natural draught boiler models, a hole must be made in the exhaust ue at a distance from the boiler equal to twice

the internal diameter of the ue.

The following parameters can be measured through this hole:

temperature of the products of combustion;

concentration of oxygen (O

) or, alternatively, carbon dioxide (CO

);

2

2

concentration of carbon monoxide (CO).

The temperature of the combustion air must be measured close to the point where the air enters the boiler. The hole,

which must be made by the person in charge of the system during commissioning, must be sealed so as to ensure that

the exhaust duct is airtight during normal operation

.

25. PUMP CAPACITY/ HEAD

A high static head pump (GRUN-

DFOS UPSO 15-50), suitable for

installation on any type of single- or

1103_0901

double-pipe heating system, is used.

The automatic air valve incorporated

in the pump allows quick venting of

O

2

the heating system.

HEAD mH

Graph 1

FLOW l/h

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

78

26. CONNECTING THE EXTERNAL SENSOR

The wiring harness leaving the control board includes two RED wires tted with faston covers. Connect the external sensor

to these two wires.

With the external sensor connected, the “kt” curve (Graph 2) can be changed by pressing

+/- .

N.B.: In case of installation in an average living unit (good perimeter insulation and radiator systems), set the “kt” climate

curve to “25”.

TM

“kt” curves

1012_0501

TM = Flow temperature range

Te

Graph 2

Te = External temperature

27. DHW EXPANSION VESSEL (AVAILABLE ON REQUEST)

DHW expansion vessel kit comprising:

- 1 stainless steel expansion vessel;

- 1 support for expansion vessel;

- 1 nipple G1/2”;

- 1 lock nut;

- 1 connection hose.

Connect the hose (supplied as an accessory in the expansion vessel kit) to the two connectors A and B as shown in gure.

The DHW expansion vessel should be mounted if:

- the pressure of the water supply or lifting system is such as to require the installation of a pressure reducer (pressure

higher than 4 bar)

- a non-return valve is tted to the water supply line

- the water supply network is insufcient for the expansion of the water contained in the storage boiler and it is necessary

to use the DHW expansion vessel.

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

79

TIPS

For the efcient operation of the expansion vessel, the pressure of the water supply must be lower than 4 bar. If it is not,

install a pressure reducer. Adjust the pressure reducer to obtain a water supply pressure less than 4 bar.

28. ANNUAL SERVICE

To optimise boiler efciency, carry out the following annual controls:

check the appearance and air-tightness of the gaskets of the gas and combustion circuits;

check the state and correct position of the ignition and ame-sensing electrodes;

check the state of the burner and make sure it is rmly xed;

check for any impurities inside the combustion chamber.

Use a vacuum cleaner to do this;

check the gas valve is correctly calibrated;

check the pressure of the heating system;

check the pressure of the expansion vessel;

check the fan works correctly;

make sure the ue and air ducts are unobstructed.

check the state of the boiler anode.

WARNINGS

Before commencing any maintenance operations, make sure the boiler is disconnected from the power supply.

Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.

29. DRAINING THE BOILER CIRCUIT AND THE STORAGE BOILER

DRAINING THE BOILER CIRCUIT

Drain the boiler by opening the tap in the hydraulic assembly.

To drain the boiler using the drain tap located at the bottom, proceed as follows (g. 14):

- close the boiler on/off valves;

- open the drain tap using an 8 mm hex wrench;

- drain the boiler;

- close the drain tap using the 8 mm hex wrench.

Figure 14

INSTALLATION INSTRUCTIONS

71.06199.02 - EN

80