PowerWalker VFI 1000RM LCD: инструкция

Раздел: Техника

Тип:

Инструкция к PowerWalker VFI 1000RM LCD

background image

EN 

Online UPS

PowerWalker   VFI 1000RM LCD

PowerWalker   VFI 1500RM LCD 

PowerWalker   VFI 2000RM LCD 

PowerWalker   VFI 3000RM LCD

   

  User Manual (EN, ES, DE, FR, IT, PT, RU) 

Uninterruptible Power Supply System

background image

EN 

Table of Contents 

1. Important Safety Warni

ng…………………………………………………

1-1. Transportation 

1-2. Preparation 

1-3. Installation 

1-4. Operation 

1-5. Maintenance, service and faults 

2. Installation and setup……………………………………………………..

2-1. Rear panel view 

2-2. Rack-mounted the UPS 

2-3. Setup the UPS 

2-4. Battery replacement 

2-5. Battery kit assembly (option) 

3. Operations…………………………………………………………………..

10 

3-1. Button operation 

10 

3-2. LCD Panel 

10 

3-3. Audible Alarm 

12 

3-4. LCD display wordings index 

12 

3-5. UPS Setting 

12 

3-6. Operating Mode Description 

15 

3-7. Faults Reference Code 

15 

3-8. Warning indicator 

16 

4. Troubleshooting…………………………………………………………....

18 

5. Storage and Maintenance

………………………………………………… 

18 

6. Specifications

………………………………………………………………. 

19 

background image

EN 

1. Important Safety Warning 

Please  comply  with  all  warnings  and  operating  instructions  in  this  manual  strictly.  Save this 

manual properly and read carefully the following instructions before installing the unit. Do not 

operate  this  unit  before  reading  through  all  safety  information  and  operating  instructions 

carefully 

1.1. Transportation 

Please  transport  the  UPS  system  only  in  the  original  package  to  protect  against 

shock and impact. 

1.2. Preparation 

Condensation  may  occur  if  the  UPS  system  is  moved  directly  from  cold  to  warm 

environment. The UPS system must be absolutely dry before being installed. Please 

allow at least two hours for the UPS system to acclimate the environment.   

Do not install the UPS system near water or in moist environments. 

Do not install the UPS system where it would be exposed to direct sunlight or near 

heater. 

Do not block ventilation holes in the UPS housing. 

1.3. Installation 

Do not connect appliances or devices which would  overload the  UPS system (e.g. 

laser printers) to the UPS output sockets.   

Place cables in such a way that no one can step on or trip over them.   

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

The UPS can be operated by any individuals with no previous experience.   

Connect the UPS system only to an earthed shockproof outlet which must be easily 

accessible and close to the UPS system.   

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your 

computer)  to  connect  the  UPS  system  to  the  building  wiring  outlet  (shockproof 

outlet).   

Please  use only VDE-tested, CE-marked power cables to connect the loads to the 

UPS system.   

When installing the equipment, it should ensure that the sum of the leakage current 

of the UPS and the connected devices does not exceed 3.5mA. 

1.4. Operation 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 

(shockproof  socket  outlet)  during  operations  since  this  would  cancel  the  protective 

earthing of the UPS system and of all connected loads.   

The  UPS  system  features  its  own,  internal  current  source  (batteries).  The  UPS 

output  sockets  or  output  terminals  block  may  be  electrically  live  even  if  the  UPS 

system is not connected to the building wiring outlet.   

In  order  to  fully  disconnect  the  UPS  system,  first  press  the  OFF/Enter  button  to 

disconnect the mains.   

Prevent no fluids or other foreign objects from inside of the UPS system.   

background image

EN 

1.5. Maintenance, service and faults 

The UPS system operates with hazardous voltages. Repairs may be carried out only 

by qualified maintenance personnel.   

Caution - 

risk of electric shock. Even after the unit is disconnected from the mains 

(building wiring outlet), components inside the UPS system are still connected to the 

battery and electrically live and dangerous.   

Before carrying out any kind of service and/or maintenance, disconnect the batteries 

and verify that no current is present and no hazardous voltage exists in the terminals 

of high capability capacitor such as BUS-capacitors.   

Only  persons  are  adequately  familiar  with  batteries  and  with  the  required 

precautionary  measures  may  replace  batteries  and  supervise  operations. 

Unauthorized persons must be kept well away from the batteries.   

Caution  -

  risk  of  electric  shock.  The  battery  circuit  is  not  isolated  from  the  input 

voltage.  Hazardous  voltages  may  occur  between  the  battery  terminals  and  the 

ground. Before touching, please verify that no voltage is present!   

Batteries may cause electric shock and have a high short-circuit current. Please take 

the  precautionary  measures  specified  below  and  any  other  measures  necessary 

when working with batteries:   

  remove wristwatches, rings and other metal objects   

  use only tools with insulated grips and handles.   

When changing batteries, install the same number and same type of batteries.   

Do  not  attempt  to  dispose  of  batteries  by  burning  them.  This  could  cause  battery 

explosion.   

Do not open  or destroy  batteries. Escaping electrolyte can cause injury to the skin 

and eyes. It may be toxic.   

Please replace the fuse only with the same type and amperage in order to avoid fire 

hazards.   

Do not dismantle the UPS system. 

background image

EN 

   

2. Installation and setup 

NOTE: 

Before installation, please inspect the unit. Be sure that nothing inside the package is 

damaged. Please keep the original package in a safe place for future use. 

NOTE:

 There  are  two  different  types  of  online  UPS:  standard  and  long-run  models.  Please 

refer to the following model table. 

Model 

Type 

Model 

Type 

1K 

Standard 

1K-L 

Long-run 

2K 

2K-L 

3K 

3K-L 

2.1. Rear panel view 

1K(L) & 2K(L)

3K(L) 

1.  Programmable outlets: connect to non-critical loads.   

2.  Output receptacles: connect to mission-critical loads. 

3.  AC input 

4.  Input circuit breaker 

5.  Network/Fax/Modem surge protection 

6.  Emergency power off function connector (EPO) 

7.  USB communication port 

8.  RS-232 communication port 

9.  SNMP intelligent slot 

10. External battery connection (only available for L model) 

2.2. Rack-Mounted the UPS 

This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this 

UPS. 

Step 1 

Step 2 

         

background image

EN 

2.3. Setup the UPS 

Step 1: Connect battery wires 

For safety consideration, the UPS is shipped out from factory without connecting battery wires. 

Before install the UPS, please follow below steps to re-connect battery wires first.   

Step 1 

Step 2 

Step 3 

Remove front panel.   

Connect the AC input and 

re-connect battery wires. 

Put the front panel back to the 

unit. 

Step 2: UPS input connection 

Plug  the  UPS  into  a  two-pole,  three-wire,  grounded  receptacle  only.  Avoid  using  extension 

cords.   

  For 200/208/220/230/240VAC models:

The power cord is supplied in the UPS package.

   

  For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input 

plug is a NEMA 5-15P for 1K and 1K-L models, NEMA 5-20P for 2K and 2K-L models.   

Note:

For Low voltage models

: Check if the site wiring fault indicator lights up in LCD panel. It 

will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer 

to Troubleshooting section). 

Please also install a circuit breaker (40A) between the mains and 

AC input in 3K model for safety operation.

Step 3: UPS output connection 

For  socket-type  outputs,  there  two  kinds  of  outputs:  programmable  outlets  and  general 

outlets.  Please  connect  non-critical  devices  to  the  programmable  outlets  and  critical 

devices to the general outlets. During power failure, you may extend the backup time to 

critical devices by setting shorter backup time for non-critical devices.   

For terminal-type input or outputs, please follow below steps for the wiring configuration: 

a) Remove the small cover of the terminal block 

b)  Suggest  using  AWG14  or  2.1mm

2

  power  cords.  Suggest  using  AWG12-10  or 

3.3mm

2

-5.3mm

2

 power cords for NEMA type. 

c)  Upon  completion  of  the  wiring  configuration,  please  check  whether  the  wires  are 

securely affixed. 

d) Put the small cover back to the rear panel. 

Step 4: Communication connection 

Communication port: 

USB port                            RS-232 port                  Intelligent slot 

To  allow  for  unattended  UPS  shutdown/start-up  and  status  monitoring,  connect  the 

communication  cable  one  end  to  the  USB/RS-232  port  and  the  other  to  the  communication 

port  of  your  PC.  With  the  monitoring  software  installed,  you  can  schedule  UPS 

shutdown/start-up and monitor UPS status through PC. 

background image

EN 

The  UPS  is  equipped  with  intelligent  slot  perfect  for  either  SNMP  or  AS400  card.  When 

installing either SNMP or AS400 card in the UPS, it will provide advanced communication and 

monitoring options.   

PS. USB port and RS-

232 port can’t work at the same time.   

Step 5: Network connection 

Network/Fax/Phone surge port

Connect a single modem/phone/fax line into surge-

protected “IN” outlet on the back panel of 

the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line 

cable.

Step 6: Disable and enable EPO function 

Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the 

wire between pin 1 and pin 2. 

Step 7: Turn on the UPS   

Press the ON/Mute button on the front panel for two seconds to power on the UPS. 

Note:  The  battery  charges  fully  during  the  first  five  hours  of  normal  operation.  Do  not 

expect full battery run capability during this initial charge period. 

Step 8: Install software 

For  optimal  computer  system  protection,  install  UPS  monitoring  software  to  fully  configure 

UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If 

not, please follow steps below to download and install monitoring software from the internet:

1. Go to the website 

http://www.power-software-download.com

2.  Click  ViewPower  software  icon  and  then  choose  your  required  OS  to  download  the 

software.   

3. Follow the on-screen instructions to install the software. 

4. When your computer restarts, the monitoring software will appear as an orange plug icon 

located in the system tray, near the clock. 

Step 8: External battery connection

 (for long-run models only) 

Follow below chart to make external   

battery connection. 

It’s in closed status for UPS 

normal operation.   

background image

EN 

                                   

2.4 Battery replacement 

NOTICE: 

This  UPS  is  equipped  with  internal  batteries  and  user  can  replace  the  batteries 

without  shutting  down  the  UPS  or  connected  loads.(hot-swappable  battery  design) 

Replacement is a safe procedure, isolated from electrical hazards.   

CAUTION!! 

Consider all warnings, cautions, and notes before replacing batteries.   

Note: 

Upon battery disconnection, equipment is not protected from power outages. 

Step 1 

Step 2 

Step 3 

Remove front panel.   

Disconnect battery wires. 

Pull out the battery box by 

removing two screws on the front 

panel.   

Step 4 

Step 5 

Step 7 

Remove the top cover of battery 

box and replace the inside 

batteries.   

After replacing the batteries, put 

the battery box back to original 

location and screw it tightly.   

Re-connect the battery wires.   

background image

EN 

Step 8 

Put the front panel back to the unit.   

2.5 Battery kit assembly (option) 

NOTICE:

  Please  assemble  battery  kit  first  before  installing  it  inside  of  UPS.  Please  select 

correct battery kit procedure below to assemble it.   

2-battery kit 

Step 1: Remove adhesive tapes.   

Step  2:  Connect  all  battery  terminals  by 

following below chart.   

Step  3:  Put  assembled  battery  packs  on 

one side of plastic shells. 

Step 4: Cover the other side of plastic shell as 

below chart. Then, battery kit is assembly well. 

Tapes 

background image

EN 

4-battery kit 

Step 1: Remove adhesive tapes.   

Step  2:  Connect  all  battery  terminals  by 

following below chart.   

Step  3:  Put  assembled  battery  packs  on 

one side of plastic shells.   

Step 4: Cover the other side of plastic shell as 

below chart. Then, battery kit is assembly well. 

6-battery kit 

Step 1: Remove adhesive tapes.   

Step  2:  Connect  all  battery  terminals  by 

following below chart.   

Step  3:  Put  assembled  battery  packs  on 

one side of plastic shells.   

Step 4: Cover the other side of plastic shell as 

below chart. Then, battery kit is assembly well. 

Tapes 

Tapes 

Tapes 

Tapes 

background image

10 

EN 

3. Operations 

3.1. Button operation 

Button 

Function   

ON/Mute Button   

  Turn  on  the  UPS:  Press  and  hold  ON/Mute  button  for  at  least  2 

seconds to turn on the UPS. 

  Mute the alarm: When the UPS is on battery mode, press and hold 

this  button  for  at  least  5  seconds  to  disable  or  enable  the  alarm 

system. But it’s not applied to the situations when warnings or errors 

occur.   

  Up key: Press this button to display previous selection in UPS setting 

mode. 

  Switch to UPS self-test mode: Press and hold ON/Mute buttons for 5 

seconds to enter UPS self-testing while in AC mode, ECO mode, or 

converter mode. 

OFF/Enter Button   

  Turn  off  the  UPS:  Press  and  hold  this  button  at  least  2  seconds  to 

turn off the UPS in battery mode. UPS will be in standby mode under 

power  normal  or  transfer  to  Bypass  mode  if  the  Bypass  enable 

setting by pressing this button.   

  Confirm selection key: Press this button to confirm selection in UPS 

setting mode.   

Select Button   

  Switch LCD message: Press this button to change the LCD message 

for input voltage, input frequency, battery voltage, output voltage and 

output frequency. It will return back to default display when pausing 

for 10 seconds.   

  Setting mode: Press and hold this button for 5 seconds to enter UPS 

setting mode when UPS is in standby mode or bypass mode.   

  Down key: Press this button to display next selection in UPS setting 

mode. 

ON/Mute + Select 

Button 

  Switch  to  bypass  mode:  When  the  main  power  is  normal,  press 

ON/Mute  and  Select  buttons  simultaneously  for  5  seconds.  Then 

UPS will enter to bypass mode. This action will be ineffective when 

the input voltage is out of acceptable range.   

3.2. LCD Panel 

background image

11 

EN 

Display   

Function   

Backup time information 

Indicates the remaining backup time in pie chart. 

Indicates the remaining backup time in numbers. 

H: hours, M: minute, S: second 

Fault information 

Indicates that the warning and fault occurs. 

Indicates the warning and fault codes, and the codes are listed in 

details in 3-5 section. 

Mute operation   

Indicates that the UPS alarm is disabled.   

Output & Battery voltage information   

Indicates the output voltage, frequency or battery voltage. 

Vac: output voltage, Vdc: battery voltage, Hz: frequency 

Load information   

Indicates the load level by 0-25%, 26-50%, 51-75%, and 

76-100%.   

Indicates overload. 

Indicates the load or the UPS output is short circuit. 

Programmable outlets information 

Indicates that programmable management outlets are working. 

Mode operation information 

Indicates the UPS connects to the mains. 

Indicates the battery is working.   

Indicates the bypass circuit is working. 

Indicates the ECO mode is enabled. 

Indicates the Inverter circuit is working. 

Indicates the output is working. 

Battery information 

Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 

76-100%. 

Indicates the battery is fault. 

Indicates low battery level and low battery voltage. 

Input & Battery voltage information 

Indicates the input voltage or frequency or battery voltage. 

Vac: Input voltage, Vdc: battery voltage, Hz: input frequency 

background image

12 

EN 

3.3. Audible Alarm   

Battery Mode 

Sounding every 4 seconds 

Low Battery 

Sounding every second 

Overload 

Sounding twice every second 

Fault 

Continuously sounding 

Bypass Mode 

Sounding every 10 seconds 

3.4. LCD display wordings index 

Abbreviation 

Display content 

Meaning 

ENA 

Enable 

DIS 

   

Disable 

ESC 

Escape 

HLS 

High loss 

LLS 

Low loss 

BAT 

Battery 

CF 

Converter 

EP 

EPO 

FA 

Fan 

TP 

Temperature 

CH 

Charger 

3.5. UPS Setting 

There are three parameters to set up the 

UPS.   

Parameter 1: It’s for program alternatives. 

There are 10

programs to set up. Refer to 

below table. 

Parameter  2  and  parameter  3  are  the 

setting  options  or  values  for  each 

program.

Parameter 1 

Parameter 2 

Parameter 3 

background image

13 

EN 

01: Output voltage setting 

Interface 

Setting 

Parameter 3: Output voltage 

For 200/208/220/230/240 VAC models, you may choose the 

following output voltage: 

200:

 present output voltage is 200Vac 

208:

 present output voltage is 208Vac 

220:

 present output voltage is 220Vac 

230:

 present output voltage is 230Vac 

240:

 present output voltage is 240Vac 

For 100/110/150/120/127 VAC models, you may choose the 

following output voltage: 

100:

 present output voltage is 100Vac 

110:

 present output voltage is 110Vac 

115: 

present output voltage is 115Vac 

120: 

present output voltage is 120Vac 

127: 

present output voltage is 127Vac

02: Frequency Converter enable/disable 

Interface 

Setting 

Parameter 2 & 3: 

Enable or disable converter mode. You may 

choose the following two options:

CF ENA: 

converter mode enable 

CF DIS: 

converter mode disable

03: Output frequency setting 

Interface 

Setting 

Parameter 2 & 3: Output frequency setting.   

You may set the initial frequency on battery mode: 

BAT 50:

 present output frequency is 50Hz 

BAT 60:

 present output frequency is 60Hz 

If converter mode is enabled, you may choose the following output 

frequency: 

CF 50: 

present output frequency is 50Hz 

CF 60: 

present output frequency is 60Hz

04: ECO enable/disable 

Interface 

Setting 

Parameter 3: 

Enable or disable ECO function. You may choose 

the following two options:   

ENA:

 ECO mode enable 

DIS: 

ECO mode disable

05: ECO voltage range setting 

Interface 

Setting 

Parameter 2 & 3: 

Set the acceptable high voltage point and low 

voltage point for ECO mode by pressing Down key or Up key.     

HLS: 

High loss voltage in ECO mode in parameter 2. 

For 200/208/220/230/240 VAC models, the setting range in 

parameter 3 is from +7V to +24V of the nominal voltage. 

For 100/110/115/120/127 VAC models, the setting range in 

parameter 3 is from +3V to +12V of the nominal voltage.   

LLS: 

Low loss voltage in ECO mode in parameter 2. 

For 200/208/220/230/240 VAC models, the setting range in 

parameter 3 is from -7V to -24V of the nominal voltage.   

For 100/110/115/120/127 VAC models, the setting voltage in 

background image

14 

EN 

parameter 3 is from -3V to -12V of the nominal voltage. 

06: Bypass enable/disable when UPS is off 

Interface 

Setting 

Parameter 3: 

Enable or disable Bypass function. You may choose 

the following two options:   

ENA:

 Bypass enable 

DIS:

 Bypass disable

07: Bypass voltage range setting 

Interface 

Setting 

Parameter 2 & 3: 

Set the acceptable high voltage point and 

acceptable low voltage point for Bypass mode by pressing the 

Down key or Up key. 

HLS: 

Bypass high voltage point 

For 200/208/220/230/240 VAC models: 

230-264:

 setting the high voltage point in parameter 3 from 230Vac 

to 264Vac.   

For 100/110/115/120/127 VAC models:   

120-132:

 setting the high voltage point in parameter 3 from 120Vac 

to 132Vac 

LLS: 

Bypass low voltage point 

For 200/208/220/230/240 VAC models: 

170-220: 

setting the low voltage point in parameter 3 from 170Vac 

to 220Vac 

For 100/110/115/120/127 VAC models:   

85-115: 

setting the low voltage point in parameter 3 from 85Vac to 

115Vac.

08: Programmable outlets enable/disable 

Interface 

Setting 

Parameter 3: 

Enable or disable programmable outlets.   

ENA:

 Programmable outlets enable 

DIS:

 Programmable outlets disable

09: Programmable outlets setting 

Interface 

Setting 

Parameter 3: 

Set up backup time limits for programmable outlets.   

0-999: 

setting  the  backup  time  limits  in  minutes  from  0-999  for 

programmable  outlets  which  connect  to  non-critical  devices  on 

battery mode.

10: Backup time setting for outlets 

Interface 

Setting 

Parameter  3: 

Set  up  backup  time  on  battery  mode  for  general 

outlets.   

0-999: 

setting the backup time in minutes from 0-999 for general 

outlets on battery mode. 

0:

When setting as “0”, the backup time will be only 10 seconds. 

999: 

When  setting  as  “999”,  the  backup  time  setting  will  be 

disabled. 

00: Exit setting 

background image

15 

EN 

3.6. Operating Mode Description 

Operating mode  Description 

LCD display   

Online mode 

When  the  input  voltage  is  within 

acceptable range, UPS will provide pure 

and  stable  AC  power  to  output.  The 

UPS  will  also  charge  the  battery  at 

online mode.   

ECO mode 

Energy saving mode:   

When the input voltage is within voltage 

regulation  range,  UPS  will  bypass 

voltage to output for energy saving.   

Frequency 

Converter mode 

When input frequency is within 40 Hz to 

70 Hz, the UPS can be set at a constant 

output frequency, 50 Hz or 60 Hz.    The 

UPS  will  still  charge  battery  under  this 

mode. 

Battery mode 

When  the  input  voltage  is  beyond  the 

acceptable  range  or  power  failure  and 

alarm is sounding every 4 second, UPS 

will backup power from battery.   

Bypass mode 

When input voltage is within acceptable 

range  but  UPS  is  overload,  UPS  will 

enter bypass mode or bypass mode can 

be set by front panel. Alarm is sounding 

every 10 second.   

Standby mode 

UPS  is  powered  off  and  no  output 

supply  power,  but  still  can  charge 

batteries. 

background image

16 

EN 

3.7. Faults Reference Code 

Fault event 

Fault code    Icon  Fault event 

Fault code    Icon 

Bus start fail 

01 

Inverter voltage Low 

13 

Bus over 

02 

Inverter output short 

14 

Bus under 

03 

Battery voltage too high 

27 

Bus unbalance 

04 

Battery voltage too low 

28 

Inverter soft start fail 

11 

Over temperature 

41 

Inverter voltage high 

12 

Over load 

43 

3.8. Warning indicator 

Warning 

Icon (flashing) 

Alarm 

Low Battery 

Sounding every second 

Overload 

Sounding twice every second 

Battery is not connected 

Sounding every second 

Over Charge 

Sounding every second 

Site wiring fault 

Sounding every second 

EPO enable 

Sounding every second 

Fan Failure 

   

Sounding every second 

Over temperature 

Sounding every second 

Charger failure 

Sounding every second 

Out of bypass voltage range 

Sounding every second 

background image

17 

EN 

4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 

below.   

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  even 

though the mains is normal.   

The AC input power is not 

connected well. 

Check  if  input  power  cord 

firmly  connected  to  the 

mains.   

The AC input is connected 

to the UPS output. 

Plug  AC  input  power  cord 

to AC input correctly.   

The  icon 

and  the  warning 

code 

  flashing  on  LCD 

display  and  alarm  is  sounding 

every second. 

EPO function is activated. 

Set  the  circuit  in  closed 

position  to  disable  EPO 

function. 

The icon 

and 

  flashing on 

LCD 

display 

and 

alarm 

is 

sounding every second. 

Line 

and 

neutral 

conductors  of  UPS  input 

are reversed. 

Rotate 

mains 

power 

socket  by  180°  and  then 

connect to UPS system. 

The  icon 

and 

  flashing 

on  LCD  display  and  alarm  is 

sounding every second. 

The  external  or  internal 

battery 

is 

incorrectly 

connected. 

Check  if  all  batteries  are 

connected well. 

Fault  code  is  shown  as  27  and 

the  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

Battery  voltage  is  too  high 

or the charger is fault. 

Contact your dealer. 

Fault  code  is  shown  as  28  and 

the  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

Battery  voltage  is  too  low 

or the charger is fault. 

Contact your dealer. 

The  icon 

  and

is 

flashing  on  LCD  display  and 

alarm  is  sounding  twice  every 

second. 

UPS is overload   

Remove 

excess 

loads 

from UPS output. 

UPS 

is 

overloaded. 

Devices  connected  to  the 

UPS are fed directly by the 

electrical  network  via  the 

Bypass. 

Remove 

excess 

loads 

from UPS output. 

After  repetitive  overloads, 

the  UPS  is  locked  in  the 

Bypass  mode.  Connected 

devices are fed directly by 

the mains. 

Remove 

excess 

loads 

from  UPS  output  first. 

Then  shut  down  the  UPS 

and restart it. 

Fault  code  is  shown  as  43  and 

The  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

The 

UPS 

shut 

down 

automatically  because  of 

overload 

at 

the 

UPS 

output. 

Remove 

excess 

loads 

from  UPS  output  and 

restart it. 

background image

18 

EN 

   

Symptom 

Possible cause 

Remedy 

Fault  code  is  shown  as  14  and 

the  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

The 

UPS 

shut 

down 

automatically 

because 

short  circuit  occurs  on  the 

UPS output. 

Check  output  wiring  and  if 

connected  devices  are  in 

short circuit status. 

Fault code is shown as 1, 2, 3, 4, 

11, 12, 13 and 41 on LCD display 

and 

alarm 

is 

continuously 

sounding. 

A  UPS  internal  fault  has 

occurred.  There  are  two 

possible results: 

1. 

The 

load 

is 

still 

supplied,  but  directly  from 

AC power via bypass.   

2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer 

Battery  backup  time  is  shorter 

than nominal value 

Batteries  are  not  fully 

charged 

Charge the batteries for at 

least  5  hours  and  then 

check  capacity.  If  the 

problem 

still 

persists, 

consult your dealer.   

Batteries defect 

Contact  your  dealer  to 

replace the battery. 

The  icon 

and  the  warning 

code 

  flashing  on  LCD 

display  and  alarm  is  sounding 

every second. 

Fan  is  locked  or  not 

working   

Check  fans  and  notify 

dealer!!   

5. Storage and Maintenance 

Operation   

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years 

at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this 

case, please contact your dealer.   

Storage   

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry 

location. During storage, recharge the battery in accordance with the following table: 

Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

   

Be sure to deliver the spent battery to a recycling facility or ship it to your 

dealer in the replacement battery packing material. 

background image

19 

EN 

6. Specifications 

MODEL 

1000 

1500 

2000 

3000 

CAPACITY* 

1000 VA / 800 W 

1500 VA / 1200 W  2000 VA / 1600 W  3000 VA / 2400 W 

INPUT 

Voltage 

Range 

Low Line Transfer 

80VAC/70VAC/60VAC/50VAC ± 5% or 160VAC/140VAC/120VAC/110VAC ± 5%   

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

Low Line Comeback 

85VAC/75VAC/65VAC/55VAC ± 5 % or 170VAC/150VAC/130VAC/120VAC± 5 %   

High Line Transfer 

150 VAC ± 5 % or 300 VAC ± 5 % 

High Line Comeback 

145 VAC ± 5 % or 290 VAC ± 5 % 

Frequency Range 

45Hz ~ 55 Hz or 56Hz ~ 65 Hz 

Phase 

Single phase with ground 

Power Factor 

 0.99 @ 220-230 VAC or 110-120 VAC 

OUTPUT 

Output voltage 

100/110/115/120/127 VAC or 200/208/220/230/240VAC 

AC Voltage Regulation   

± 1% (Batt. Mode) 

Frequency Range   

(Synchronized Range) 

48 ~ 52 Hz or 58 ~ 62 Hz 

Frequency Range (Batt. Mode) 

50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz 

Current Crest Ratio 

3:1 

Harmonic Distortion 

 2%    (Linear load)   

  8% max (Bat mode before shut down) 

Transfer 

Time 

AC Mode to Batt. Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

86 % 

88 % 

Battery Mode 

83 % 

85 % 

BATTERY 

Standard 

Model 

Battery Type 

12 V / 7AH 

12 V / 9AH 

12 V / 7 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% capacity (Typical) 

Charging Current   

1.0 A(max.) 

Charging Voltage   

41.1 VDC± 1% 

82.1VDC ± 1% 

82.1VDC ± 1% 

Long-run 

Model 

Battery Type & 

Numbers 

Depending on the capacity of external batteries 

Charging Current   

8.0 A(max.) 

Charging Voltage 

41.1 VDC± 1% 

82.1VDC ± 1% 

82.1VDC ± 1% 

PHYSICAL 

Standard 

Model 

Dimension, D X W X H 

mm   

480 x 438 x 88 

600 x 438 x 88 

600 x 438 x 88 

Net Weight (kgs) 

18.4 

18.5 

25.7 

29 

Long-run 

Model 

Dimension, D X W X H 

mm   

480 x 438 x 88 

600 x 438 x 88 

600 x 438 x 88 

Net Weight (kgs) 

11.3 

10.7 

14.6 

14.8 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008/7, Linux, Unix and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 

208VAC. 

background image

ES 

  SAI Online 

PowerWalker   VFI 1000RM LCD

PowerWalker   VFI 1500RM LCD 

PowerWalker   VFI 2000RM LCD 

PowerWalker   VFI 3000RM LCD

   

Manual de usuario  Sistema de Alimentación Ininterrumpida 

Аннотация для PowerWalker VFI 1000RM LCD в формате PDF