De Dietrich MS 24 BIC FF – страница 4

Инструкция к Водонагревателю De Dietrich MS 24 BIC FF

background image

61

71.06199.02 - EN

OPERATING INSTRUCTIONS

To light the boiler correctly, proceed as follows:

1)  power the boiler

2) open the gas tap;

3) press the button (

and switch the boiler to Summer ( ), Winter (  

) or heating only (

);

4)  press the heating circuit (

+/-

) and domestic hot water circuit (

) temperature adjustment buttons ( ) in order to ignite 

the main burner. 

  When the boiler is lit, the symbol ( ) will appear on the display.

  In the Summer position ( ) the main burner will only ignite if a DHW tap is opened.

WARNING

During initial ignition, the burner may not ignite (causing the boiler to shut down) until any air in the gas pipes is vented. In 

this case, repeat the ignition procedure until gas reaches the burner. Press button ( ), for at least 2 seconds.

3. COMMISSIONING THE BOILER

Operation in the heating mode

Flame present (burner on)

No flame (ignition failure)

Operation in the DHW mode

Generic fault

No water (Low system pressure)

Numerical signal (Temperature, fault code, etc.)

RESET

BUTTON KEY

Figure 1

SYMBOL KEY

On / Off / Summer / Winter / heating only

(

+/-

) : CH temperature adjustment

(

+/-

) : DHW temperature adjustment

Reset

Information

0805_2302 / C

G_2072

background image

62

71.06199.02 - EN

OPERATING INSTRUCTIONS

4. ADJUSTING ROOM TEMPERATURE AND DHW TEMPERATURE

The system must be fitted with a room thermostat for controlling indoor temperature.

Adjust the room temperature (

) and the DHW temperature (

) by pressing the respective

+/-

(figure 1). The ignition 

of the burner is shown on the display with the symbol ( ) as described in section 3.

HEATING

While the boiler is operating in the heating mode, the display (figure 1) shows the flashing symbol (

) and the heating 

delivery temperature (°C).

DOMESTIC HOT WATER

While the boiler is operating in the DHW mode, the display (figure 1) shows the flashing symbol (

) and the DHW output 

temperature (°C).

Press this button to set the following operating modes:

• SUMMER

• WINTER

• HEATING ONLY

• OFF

In the 

SUMMER

 mode, the display shows  (

). The boiler satisfies requests for DHW only while central heating is NOT 

enabled (ambient frost protection function active).

In the 

WINTER

 mode, the display shows (

). The boiler satisfies requests for both DHW and central heating (am-

bient frost protection function active).

In the 

HEATING ONLY

 mode, the display shows (

). The boiler satisfies requests for central heating only (ambient frost 

protection function active).

In the 

OFF

 mode, the display shows neither of the above two symbols ( 

) (

). In this mode, only the ambient frost 

protection function is active while requests for DHW and central heating are not satisfied.

5. DESCRIPTION OF BUTTON   (Summer - Winter - Heating only - Off)

WARNING

Disconnect the boiler from the mains power supply using the two-pole switch.

IMPORTANT:

 Regularly check that the pressure displayed on the pressure gauge is 0.7 - 1.5 bar, with the boiler cold. 

In case of overpressure, open the boiler drain tap. In case of insufficient temperature, open the boiler filling tap (figure 3).

Open the tap very slowly in order to vent the air.

6. FILLING THE SYSTEM

background image

63

71.06199.02 - EN

OPERATING INSTRUCTIONS

To turn off the boiler, disconnect the electric power supply. In “OFF” mode (section 5) the boiler remains off (the display 

indicates OFF) though the electrical circuits remain live and the frost protection device is enabled (section 9).

7. TURNING OFF THE BOILER 8. GAS CONVERSION

The boilers can operate both on natural gas and 

LPG

.

All gas conversions must be made by an authorised Service Engineer.

The boiler is fitted with a hydraulic pressure gauge which prevents the boiler from working if there is no water.

N.B.:

 In case pressure drops occur frequently, have the boiler checked by an authorised Service Engineer.

A: 

System emptying tap 

B:

 Boiler emptying tap 

C:

 System filling tap

D:

 Pressure gauge

Figure 2

Do not drain the whole system as filling up with water again causes unnecessary and harmful scale to build up inside the 

boiler and the heating elements. If the boiler is not used during winter and is therefore exposed to the danger of frost, add 

some specific anti-freeze to the water in the system (e.g.: propylene glycol coupled with corrosion and scale inhibitors).

The electronic boiler management system includes a “frost protection” function for the heating system which, when delivery 

temperature falls below 5°C, operates the burner until a delivery temperature of 30°C is reached.

The frost protection function is enabled if:

*   the boiler is electrically powered;

*   the gas tap is open;

*   the system is at the correct pressure;

*   the boiler is not blocked.

9. PROLONGED SHUTDOWN. FROST PROTECTION

background image

64

71.06199.02 - EN

OPERATING INSTRUCTIONS

10. TROUBLESHOOTING

N.B.:

 in case of a fault, the display backlighting flashes together with the error code.

To keep the boiler efficient and safe, have it checked by the authorised Service Centre at the end of every operating period.

Careful servicing ensures economical operation of the system.

Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily flammable cleaners (e.g.: petrol, 

alcohol, and so on). Always switch off the appliance before cleaning it (see section 7 Switching off the boiler).

11. ROUTINE MAINTENANCE INSTRUCTIONS

Faults are shown on the display with an error code (e.g.: E 01):

CODE 

DISPLAYED

FAULT

CORRECTIVE ACTION

E01

Failed ignition shutdown

Press and hold down “

R

” for at least 2 seconds. If this fault persists, call the 

Authorised Service Centre.

E02

Safety thermostat tripped

Press and hold down “

R

” for at least 2 seconds. If this fault persists, call the 

Authorised Service Centre.

E03

Flue thermostat/ flue pressure 

switch tripped

Call the Authorised Service Centre.

E04

Shutdown after 6 consecutive 

flame losses

Press and hold down “

R

” for at least 2 seconds. If this fault persists, call the 

Authorised Service Centre.

E05

Flow sensor failure

Call the Authorised Service Centre.

E06

DHW sensor fault

Call the Authorised Service Centre.

E10

Hydraulic pressure switch 

block

Check that the pressure in the system is correct; See section 6. If this fault 

persists, call the Authorised Service Centre.

E25/E26

Probable blocked pump safety 

trip

Call the Authorised Service Centre.

E35

Parasite flame (flame error)

Press and hold down “

R

” for at least 2 seconds. If this fault persists, call the 

Authorised Service Centre.

E96

Switching off due to reductions 

in power supply

RESET is automatic. If this fault persists, call the Authorised Service Centre

To RESET the boiler, press and hold down “R” for at 

least 2 seconds. If this fault persists, call the Authorised 

Service Centre.

N.B.:

 5 reset attempts can be performed after which 

the boiler shuts down. To reset again, switch off the 

boiler for a few seconds.

Figure 3

0607_1205

RESETTABLE

faults

background image

65

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

The following notes and instructions are addressed to fitters to allow them to carry out trouble-free installation. Instructions 

for igniting and using the boiler are contained in the ‘Instructions for Users’ section.

•   This boiler can be connected to any type of double- or single-pipe convector plate, radiator or thermoconvector. Design 

the system sections as usual, though, bearing in mind the available flow-head at the plate, as shown in section 25.

•   Do not leave any packaging (plastic bags, polystyrene, etc.) within reach of children, as it is a potential source of danger.

•   Initial lighting of the boiler must be carried out by an authorised Service Engineer, as indicated on the attached sheet.

Failure to observe the above will render the guarantee null and void.

ADDITIONAL PUMP WARNING

If an additional pump is used on the heating system, position it on the boiler return circuit. This will allow the correct 

operation of the water pressure switch.

SOLAR WARNING

if the instantaneous (mixed) boiler is connected to a system with solar panels, the maximum temperature of the domestic 

hot water entering the boiler must not exceed 

60°C

.

12. GENERAL INFORMATION

background image

66

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure.

It must be connected to a central heating system and to a domestic hot water supply system according to its performance 

and power output.

Do the following before connecting the boiler:

a)  Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings 

on the packaging and the rating plate on the appliance.

b)  Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gases 

from other appliances are expelled through the same flue duct, unless the latter has been specially designed to collect 

exhaust gas from more than one appliance, in compliance with current laws and regulations.

c)  Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual products 

of combustion may detach from the walls during operation and obstruct the flow of fumes.

To ensure correct operation and maintain the warranty, observe the following precautions:

1.  DHW circuit:

1.1. 

If the water is harder than 20 °F (1 °F = 10 mg calcium carbonate per litre of water), install a polyphosphate dispenser 

or an equivalent treatment system, compliant with current regulations.

1.2. 

Thoroughly flush the system after installation of the appliance and before use.

1.3. 

The materials used for the product’s DHW circuit comply with Directive 98/83/CE.

2.  Heating circuit

2.1. new system

Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual 

thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, plastic 

and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products are:

SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliance 

with the manufacturers’ instructions.

2.2. existing system:

Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable 

proprietary products as described in section 2.1.

To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such 

as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with the 

manufacturers’ instructions.

Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g. 

overheating and excessive noise of the heat exchanger).

Failure to observe the above will render the warranty null and void

.

13. INSTRUCTIONS PRIOR TO INSTALLATION 13. INSTALLAZIONE DELLA CALDAIA  14. INSTALLING THE BOILER 

After deciding the exact location of the boiler, make sure there is sufficient room to perform maintenance operations (at 

least 450 mm of headroom is required in order to replace the expansion vessel).

Connect the system to the gas and water inlets present on the lower bar of the template. Fit two G3/4 taps (flow and 

return) on the central heating circuit; these taps make it possible to carry out important operations on the system without 

draining it completely. If you are either installing the boiler on an existing system or replacing one, as well as the above, 

fit a settling tank under the boiler on the system return line in order to collect any deposits and scale circulating in the 

system after flushing. After fixing the boiler to the template, connect the flue and air ducts, supplied as accessories, as 

described in the following sections.

If the model 

24 BIC

 natural draught boiler is installed, connected it to the flue with a metal pipe resistant to normal me-

chanical stress, heat, products of combustion and relative condensate.

IMPORTANT

After filling the boiler, vent the entire internal circuit and the system as follows:

•  close the gas on-off valve;

•   power the boiler.

•   open the vent valve on the pump body;

•   press (

) to set the boiler in the “WINTER” operating mode;

•   send a heat demand from the room thermostat;

•   open a hot water tap to alternate CH demand with DHW demand;

•   after a few ignition attempts the boiler will shut down (error E01 appears on the display);

•   to rest, press and hold down “

R

” for at least 2 seconds;

•   repeat the procedure at least another two times;

•   close the vent valve.

After venting the boiler circuit, proceed with initial lighting.

background image

67

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

EXPANSION VESSEL

The boiler features a standard 7.5-litre expansion vessel with a pre-charge pressure of 1 bar. The maximum volume of water in 

the system is calculated according to hydrostatic pressure at an average water temperature of 80°C (flow: 95°C return: 75°C).

Hydrostatic pressure (m)

5

6

7

8

9

10

Maximum system volume (l)

138

131

119

107

97

87

G”3/4 HEATING FLOW

G”1/2 DOMESTIC HOT WATER OUTLET

G”3/4 HEATING RETURN

G”1/2 DOMESTIC COLD WATER INLET

G”3/4 GAS INLET TO BOILER

WARNING

Tighten the boiler nipple water connections with care (maximum tightening torque 30 Nm).

Figure 4

background image

68

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

14. DIMENSIONI CALDAIA  15. DIMENSIONS OF BOILER 

Figure 5

24 BIC FF

24 BIC

CG_1848 / 1104_0702

CG_1848 / 1104_0703

16. INSTALLING THE FLUE AND AIR DUCTS

Boiler model

Length (m)

Use of DIAPHRAGM

on INLET LINE  

A

24 BIC FF

0,5

73

0,5 ÷ 2

80

2 ÷ 4

No

If fumes are discharged outside the building, the flue-air duct must protrude 

at least 18 mm from the wall to allow an aluminium weathering surround to be 

fitted and sealed to avoid water infiltrations.

Make sure there is a minimum upward slope towards the outside of 1 cm per 

metre of duct.

  

A 90° curve reduces total duct length by 1 metre.

  

A 45° curve reduces total duct length by 0.5 metres.

The first 90° curve is not considered when calculating the maximum avai-

lable length.

Figure 7

Connector

0805_2901 / C

G_2073

Model 24 BIC FF 

The boiler is easy and flexible to install thanks to the extensive range of available 

accessories, as described below.

The boiler has been designed for connection to a vertical or horizontal coaxial 

flue-air duct. A splitting kit is also available if separate ducts are required.

Only accessories supplied by the manufacturer must be used for installation!

WARNING: To optimise operating safety, make sure the flue ducts are firmly 

fixed to the wall with suitable brackets.

… COAXIAL FLUE-AIR DUCT (CONCENTRIC)

This type of duct is used to discharge exhaust fumes and draw combustion air 

both outside the building and if a LAS flue is fitted.

The 90° coaxial curve allows the boiler to be connected to a flue-air duct in any 

direction as it can be rotated by 360°. It can also be used as a supplementary 

curve combined with a coaxial duct or a 45° curve.

Figure 6

background image

69

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

16.1 HORIZONTAL FLUE INSTALLATION EXAMPLES

16.2 LAS FLUE DUCT INSTALLATION EXAMPLES C42 TYPE

16.3 VERTICAL FLUE INSTALLATION EXAMPLES

This type of installation can be carried out on either a flat or a pitched roof by fitting a flue terminal and a special weathering 

surround with sleeve (both available on request).

0503_0908/CG1641

0512_2001

For detailed installation instructions, consult the technical data provided with the accessories.

0503_0907/CG1640

L max = 10 m (Ø 80/125 mm)

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)  

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)

L max = 4 m (Ø 60/100 mm)

8 m (Ø 80/125 mm)

L max = 3 m (Ø 60/100 mm)

7 m (Ø 80/125 mm)

L max = 3 m (Ø 60/100 mm)

7 m (Ø 80/125 mm)

L max = 8 m (Ø 80/125 mm)

L max = 9 m (Ø 80/125 mm)

background image

70

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

… SEPARATE FLUE AND AIR DUCTS

This type of installation makes it possible to discharge exhaust fumes both outside the building and into single flue ducts. 

Comburent air can be drawn in at a different location from that of the flue terminal. The splitting kit comprises a flue duct 

adaptor (100/80) and an air duct adaptor. For the air duct adaptor, fit the screws and seals previously removed from the cap.

The 90° curve allows the boiler to be connected to a flue-air duct in any direction as it can be rotated by 360°. It can also 

be used as a supplementary curve combined with a duct or a 45° curve.

•   A 90° curve reduces total duct length by 0.5 metres.

• A 45° curve reduces total duct length by 0.25 metres.

The first 90° curve is not considered when calculating the maximum available length.

Boiler model

(L1+L2)

Position 

of air regulator

    CO

2

 %

G20

G31

24 BIC FF

0 ÷ 20

1

6,1

8,7

20 ÷ 30

2

Adjusting the air regulator for separate flues

This regulator must be adjusted to optimise combustion efficiency and parameters.

After turning the air intake connecter, which can be mounted both to the right and the left of the exhaust flue duct, suitably 

adjust the excess air according to the total length of the combustion exhaust and inlet flue ducts.

Turn this regulator anticlockwise to decrease the excess of comburent air and vice-versa to increase it.

To fine tune, use a combustion product analyser to measure the amount of CO

in the fumes at maximum heat capacity, 

and, if a lower value is measured, gradually adjust the air regulator until the amount of CO

2

 indicated in the following table 

is measured.

To mount this device correctly, consult the relative instructions.

Figure 8

CG_1145 / 1104_0801

connector

aperture

index

background image

71

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

16.5 HORIZONTAL SEPARATE FLUE INSTALLATION EXAMPLES - C82

IMPORTANT

 -

 Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length. 

In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.

N.B.:

For the C52 type, do not fit the flue and air duct terminals on opposite walls of the building.

The inlet flue must have a maximum length of 10 metres for C52 fumes outlets. 

If the discharge duct is longer than 6 metres, install the condensate collection kit, supplied as an accessory, near the boiler

16.4 DIMENSIONS OF SEPARATE OUTLETS

L max = 10 m   

(L1 + L2) max  = 30 m   

1010_0102/CG1643

CG_1643_FR / 1010_0101

IMPORTANT:

 if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct 

passes through building walls. For detailed installation instructions, consult the technical data provided with the accessories.

CG_2344 / 1103_3002

background image

72

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

17. ELECTRICAL CONNECTIONS 18. CONNECTING THE ROOM THERMOSTAT

•   Access the power supply terminal block (figure 9) as described in the previous section;

•   remove the jumper on terminals (1) and (2);

•   thread the two-wire cable through the grommet and connect it to these two terminals.

This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current 

safety regulations.

Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct 

LIVE-NEUTRAL polarity.

Use a double-pole switch with a contact separation of at least 3 mm

. When replacing the power supply cable, fit a 

harmonised HAR H05 VV-F’ 3x0.75mm

2

 cable with a maximum diameter of 8 mm.

…Access to the power supply terminal block

•   disconnect the boiler from the mains power supply using the two-pole switch;

•   remove the two screws fixing the control panel to the boiler;

•   rotate the control panel;

•   remove the cover and access the wiring area (figure 9).

The 2A fast-blowing fuse is incorporated in the power supply terminal block (to check and/or replace the fuse, pull out 

the black fuse carrier).

IMPORTANT:

respect polarity 

L

 (LIVE) -

N

 (NEUTRAL).

(L) = 

Live

 (brown)

(N) = 

Neutral

 (blue)

    = 

Earth

 (yellow-green)

(1) (2) =   

Contact for room thermostat

Figure 9

CG_1853 / 1103_2302

background image

73

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

19. GAS CONVERSION

The authorised Technical Assistance Service can convert this boiler to natural gas (

G. 20

) or liquid gas (

G.31

). 

Carry out the following operations:

A) replace the nozzles of the main burner and the gas diaphragm (if fitted); 

B)  new max. and min. calibration of the pressure regulator.

A) Replace the burner nozzles

•   carefully pull the main burner off its seat;

•   replace the main burner nozzles making sure to fully tighten them to prevent gas leaks. Nozzle diameters are specified 

in table 2.

•   replace the gas membrane located on the gas valve (figure 10). The diameter of the membrane is specified in table  2.

Attention: 

it is not necessary to change parameter F02.

B) Calibrate the pressure regulator

•   connect the positive pressure test point of a differential pressure gauge (possibly water-operated) to the gas valve 

pressure test point (

Pb

) (Figure 10). Only for models with sealed chambers, connect the negative pressure test point of 

the manometer to a “T” fitting in order to join the boiler adjustment outlet, the gas valve adjusting outlet (Pc) and the 

pressure gauge. (The same measurement can be made by connecting the pressure gauge to the pressure test point 

(

Pb

) after removing the front panel of the sealed chamber);

  Measuring burner pressure using methods other than those described could lead to incorrect results as the low pressure 

created by the fan in the sealed chamber would not be taken into account.

B1) Adjustment to nominal heat output:

•   open the gas tap and switch the boiler to the Winter mode;

•   take the boiler to maximum power as described in section 19.1;

•   remove the modulator cover;

•   adjust the tube brass screw (a) until the pressure values shown in table 1 are obtained;

•   make sure that the dynamic inlet pressure of the boiler, measured at the gas valve pressure test point (Pa) (Figure 10) 

is correct (37 mbar for propane or 20 mbar for natural gas).

B2) Adjustment to reduced heat output:

•   disconnect the modulator power cable and unscrew the screw (b) until a pressure value corresponding to reduced heat 

output is achieved (see tab. 1);

•   reconnect the cable;

•   mount the modulator cover and seal.

B3) Final checks

•   attach the additional plate supplied with the transformer, specifying the type of gas and the calibration performed.

ATTENTION

If the natural gas inlet pressure is too low (less than 17 mbar) remove the gas diaphragm installed over the gas valve (fig. 

10) and set parameter 

F02=00

 on the electronic board (§21). 

Figure 10

gas valve 

mod. SIGMA 845

b

a

0605_1502

Figure 11

gas diaphragm

CG_2347 / 1104_0406

background image

74

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

19.1 GAS VALVE CALIBRATION FUNCTION

Note:

The function is automatically deactivated after a period of 15 minutes, at the end of which the electronic board returns to 

its operating status prior to the activation of the function or prior to reaching the set maximum temperature.

To simplify calibration of the gas valve, the calibration function may be set directly 

on the boiler control panel as follows:

a)

 hold down the buttons 

 and 

 together for at least 6 seconds; 

b)

 after about 6 seconds, the symbols 

 flash;

c)

  the display shows, at intervals of one second, “

100

” and the 

flow temperature

.

  In this phase, the boiler works at the maximum heating output (100%). 

d)

 press 

+/-

   to immediately set the power of the boiler (100% or 0%);

e)

  adjust the 

“Pmax/Pmin”

 screw (figure 10) to set the burner pressure value as 

described in table 1.

  To adjust pressure at maximum power, turn the “

Pmax

” screw (fig. 10) clockwise 

to increase or anti-clockwise to decrease pressure at the burner.

  To adjust pressure at minimum power, turn the “

Pmin

” screw (fig. 10) clockwise 

to increase or anti-clockwise to decrease pressure at the burner.

f)

 press 

+/-

 to gradually set the desired power level (interval = 1%).

Press the button   to leave the function.

0805_2302 / 1002_1201

Consumption 15°C-1013 mbar

24 BIC FF - 24 BIC

G20

G31

Rated power

2,73 m

3

/h

2,00 kg/h

Reduced power

1,26 m

3

/h

0,92 kg/h

p.c.i.

34,02 MJ/m

3

46,34 MJ/kg

Table 2

* 1 mbar = 10,197 mmH

2

O

Table of burner nozzles

24 BIC FF

24 BIC

gas type

G20

G31 

G20

G31

diameter of nozzles (mm)

1,18

0,69 

1,18

0,69

Burner pressure (mbar*)

REDUCED HEAT OUTPUT

1,7

6,9

1,6

6,6

Burner pressure (mbar*)

RATED HEAT OUTPUT

7,8

24,7

7,5

18,1

Diameter of gas diaphragm (mm)

4,2

3,5

4,2

3,5

N° nozzles

18

Table 1

background image

75

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

20. VISUALISATION OF PARAMETERS ON THE DISPLAY (“INFO” FUNCTION)

Press “

i

” for at least 5 seconds to visualise certain boiler information on the display on the front panel of the boiler.

Press buttons   (

+/-

) to display the following information:

A00: 

current DHW temperature (°C);

A01: 

current external temperature (°C) (with external sensor connected);

A02: 

modulation current value (100% = 310 mA);

A03: 

power range (%) (MAX R);

A04: 

heating setpoint temperature (°C) - - If the external sensor is connected, the value of the “

kt

” curve is displayed 

(section 26);

A05: 

current heating delivery temperature (°C);

A06: 

DHW temperature setpoint (°C);

A07: 

— — ;

A08: 

value (l/minx10) of the DHW flow rate;

A09: 

last error that occurred in the boiler.

This function remains active for 3 minutes. It is possible to interrupt the “INFO” function in advance by pressing button  

(

i

) for at least 5 seconds, or turning off the power to the boiler.

N.B:

 when the “INFO” function is enabled, the message “A00”, alternating with the boiler delivery temperature, 

is shown on the display (figure 12):

0605_2204 / CG_1808

Figure 12

background image

76

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

Description of parameters

Factory settings

24 BIC FF

24 BIC

F01

Type of boiler

10

 = sealed chamber 

20

 = atmospheric chamber

10

20

F02

Gas used

00

 = METHANE

01

 = LPG 

02

 = METHANE (WITH DIAPHRAGM)

02

F03

Hydraulic system

15

F04

Setting programmable relay 1 (See SERVICE instructions)

00

 = no associated function  

01

 = condominium alarm   

02

 = ambient fan

03

 = not used  

04

 = zone pump controlled by room thermostat (230V)  

05

 = not used 

04

F05

Setting programmable relay 2 (DHW pump)

03

F06

Maximum CH setpoint (°C)

00

 = 85°C - 

01

 = 45°C (function unavailable)

00

F07

DHW inlet priority configuration

00

F08

CH max. output 

(0-100%)

100

F09

DHW max. output 

(0-100%)

100

F10

Min. heating output 

(0-100%)

00

F11

Delay prior to new ignition in CH mode 

(00-10 minutes) - 00=10 seconds

03

F12

Diagnostics (See SERVICE Instructions)

--      

F13-F14-F15

Factory settings (no change)

00      

F16

Anti-legionella function

00

 = disabled

55...67

 = enabled (setpoint °C) 

00

F17

CH pressure sensor selection

00

 = hydraulic pressure sensor 

01

 = hydraulic differential pressure sensor 

00

F18

Manufacture information 

00

21. PARAMETER SETTINGS

To set the boiler parameters, press (

  ) and (

) together and hold down for at least 6 seconds. When the function is 

activate, the “

F01

” appears on the display alternating with the value of the parameter shown.

Edit parameters

•  Press  (

+/–

) to scroll through the parameters;

•  Press  (

+/–

) to edit each parameter;

•  Press 

 (

)

, to save the changes. “

MEM

” appears on the display;

•  Press 

(

i

)

,

 to exit without saving. “

ESC

” appears on the display.

22. ADJUSTMENT AND SAFETY DEVICES

The boiler has been designed in full compliance with European reference standards and in particular is fitted with the 

following:

•  Air pressure switch (model 24 

BIC FF)

  This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.

  In the event of one or more of the following faults:

•  flue terminal obstructed

•  venturi tubes obstructed

•  fan blocked

•  venturi tube connection - pressure switch tripped

the boiler remains on standby and error code E03 is displayed (see table in section 10).

background image

77

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

•  Fumes thermostat (model 24 

BIC)

  This device has a sensor positioned on the left section of the fumes hood and shuts off the gas flow to the main burner 

if the flue is obstructed and/or if there is no draught.

  In these conditions the boiler shuts down and displays error code E03 (section 10).

  After eliminating the problem, press button ( ), for at least 2 seconds to re-ignite immediately.

It is forbidden to disable this safety device

•  Safety thermostat

  Thanks to a sensor placed on the CH flow line, this thermostat interrupts the flow of gas to the burner if the water in 

the primary circuit overheats. In these conditions, the boiler is blocked and only after the fault has been eliminated can 

it be ignited again by pressing ( ), for at least 2 seconds.

It is forbidden to disenable this safety device

•  Flame ionization detector

  The flame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas 

failure or incomplete ignition of the burner.

  In these conditions, the boiler is blocked after 3 ignition attempts.

  Press ( ), for at least 2 seconds to re-establish normal operating conditions.

•  Hydraulic pressure switch

  This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.

•   Pump overrun for heating circuit

  The electronically-controlled pump post-circulation function lasts 180 seconds and is enabled, in the heating mode, if 

the ambient thermostat causes the burner to go out.

•   Pump overrun for DHW circuit

  The electronically-controlled pump post-circulation function lasts 30 seconds and is enabled, in the DHW mode, if the 

probe causes the burner to go out.

•   Frost protection device (CH and DHW systems)

  The electronic boiler management system includes a “frost protection” function for the heating system which, when 

delivery temperature falls below 5°C, operates the burner until a delivery temperature of 30°C is reached.

  This function is enabled when the boiler is switched on, the gas supply is open and the system is correctly pressurised.

•   Water not circulating in primary circuit (pump probably blocked)

  If there is insufficient or no water circulating in the primary circuit, the boiler blocks and the error code E25 is shown on 

the display (section 10).

•   Anti-block pump function

  If no heat demand is received for 24 consecutive hours, in the heating mode, the pump will automatically start and 

operate for 10 seconds. This function is operative when the boiler is powered.

• Three-way valve anti-blockage function

  If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This 

function is operative when the boiler is powered.

•   Hydraulic safety valve (heating circuit)

  This device is set to 3 bar and is used for the heating circuit

.

Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.

N.B.: 

domestic hot water is guaranteed even if the NTC sensor develops a fault. In this case, temperature is controlled 

by the delivery sensor.

background image

78

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

To measure combustion efficiency and the toxicity of the products of combustion, the boiler is fitted with two dedicated 

test points.

One connection point is connected to the exhaust duct and is used to measure combustion efficiency and the toxicity of 

the products of combustion.

The other is connected to the air intake circuit and is used to check for the presence of any products of combustion 

circu¬lating in installations with co-axial flues.

The following parameters can be measured using the test point connected to the exhaust duct:

•  temperature of the products of combustion;

•   concentration of oxygen (O

2

) or, alternatively, carbon dioxide (CO

2

);

•   concentration of carbon monoxide (CO).

The temperature of the comburent air must be measured on the test point located on the air intake flue by inserting the 

measurement sensor by about 3 cm. 

N.B.:

 to regulate the rated power, see chapter 19 (B1)

For natural draught boiler models, a hole must be made in the exhaust flue at a distance from the boiler equal to twice 

the internal diameter of the flue.

The following parameters can be measured through this hole:

•  temperature of the products of combustion;

•  concentration of oxygen (O

2

) or, alternatively, carbon dioxide (CO

2

);

•  concentration of carbon monoxide (CO).

The temperature of the combustion air must be measured close to the point where the air enters the boiler. The hole, 

which must be made by the person in charge of the system during commissioning, must be sealed so as to ensure that 

the exhaust duct is airtight during normal operation.

24. CHECKING COMBUSTION PARAMETERS 25. PUMP CAPACITY/ HEAD

A high static head pump (GRUN-

DFOS UPSO 15-50), suitable for 

installation on any type of single- or 

double-pipe heating system, is used. 

The automatic air valve incorporated 

in the pump allows quick venting of 

the heating system.

Graph 1

FLOW l/h

HEAD mH

2

O

1103_0901

23. POSITIONING THE IGNITION AND FLAME-SENSING ELECTRODE

Figure 13

9912070100

background image

79

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

26. CONNECTING THE EXTERNAL SENSOR

The wiring harness leaving the control board includes two RED wires fitted with faston covers. Connect the external sensor 

to these two wires.

With the external sensor connected, the “

kt

” curve (Graph 2) can be changed by pressing 

+/-

.

N.B.: In case of installation in an average living unit (good perimeter insulation and radiator systems), set the “

kt

” climate 

curve to “25”.

TM

 = Flow temperature range

Te

 = External temperature

Graph 2

TM

Te

“kt” curves

1012_0501

DHW expansion vessel kit comprising:

- 1 stainless steel expansion vessel;

- 1 support for expansion vessel;

- 1 nipple G1/2”;

- 1 lock nut;

- 1 connection hose.

27. DHW EXPANSION VESSEL (AVAILABLE ON REQUEST)

Connect the hose (supplied as an accessory in the expansion vessel kit) to the two connectors A and B as shown in figure.

The DHW expansion vessel should be mounted if:

-   the pressure of the water supply or lifting system is such as to require the installation of a pressure reducer (pressure 

higher than 4 bar)

-   a non-return valve is fitted to the water supply line

-   the water supply network is insufficient for the expansion of the water contained in the storage boiler and it is necessary 

to use the DHW expansion vessel.

background image

80

71.06199.02 - EN

INSTALLATION INSTRUCTIONS

To optimise boiler efficiency, carry out the following annual controls:

•   check the appearance and air-tightness of the gaskets of the gas and combustion circuits;

•   check the state and correct position of the ignition and flame-sensing electrodes;

•   check the state of the burner and make sure it is firmly fixed;

•   check for any impurities inside the combustion chamber. 

  Use a vacuum cleaner to do this;

•   check the gas valve is correctly calibrated;

•   check the pressure of the heating system;

•   check the pressure of the expansion vessel;

•   check the fan works correctly;

•   make sure the flue and air ducts are unobstructed.

•   check the state of the boiler anode.

WARNINGS

Before commencing any maintenance operations, make sure the boiler is disconnected from the power supply.

Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.

  

28. ANNUAL SERVICE

TIPS

For the efficient operation of the expansion vessel, the pressure of the water supply must be lower than 4 bar. If it is not, 

install a pressure reducer. Adjust the pressure reducer to obtain a water supply pressure less than 4 bar.

DRAINING THE BOILER CIRCUIT

Drain the boiler by opening the tap in the hydraulic assembly. 

To drain the boiler using the drain tap located at the bottom, proceed as follows (fig. 14):

-   close the boiler on/off valves;

-   open the drain tap using an 8 mm hex wrench;

-   drain the boiler;

-   close the drain tap using the 8 mm hex wrench.

29. DRAINING THE BOILER CIRCUIT AND THE STORAGE BOILER

Figure 14