YUMA
Condensate removal pump
Installation and operating guide
The YUMA is a self-contained
condensate removal system for
use directly inside the tubing
chase of high-wall-mount air
conditioners.
2
3
4
5
6
7
1
9
10 11 12 13 14
8
16 17 18 19 20
15
1
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
30
40
50
10
60
20
0
0
0
0
Vertical lift
(m)
(ft)
F
lo
w
r
at
e
(l
/h
)
(U
S
g
al
/h
))
0m Horiz
50m Horiz
100m Horiz
Capacity
Specifications
Power supply:
120/240 Vac, 50/60 Hz Auto sensing
Power consumption: 16 W max., 0.25 W when idle
Alarm relay:
5A, 30Vdc, 250Vac Break on fault
Capacity:
12 litres/hour max. (3.17 US gal/h)
Maximum head:
Vertical >20 m (65 ft), Horizontal >100 m (328 ft)
Suction 1 m max. (3.28 ft)
Ambient temp:
0 - 40°C
Water temp:
25°C max.
Material:
Flame retardant ABS UL94 5VA
Discharge tube:
6 mm (1/4”) ID
Dimensions:
175 x 46 x 40 mm (6.9” x 1.8” x 1.6”)
IP:
44
GB
1

SAFETY INSTRUCTIONS AND WARNING
Under normal use this equipment requires no user intervention. Installation, both fixing
and electrical, and maintenance work shall be carried out only by the manufacturer or
by its service center or in any case by a person having similar skills, so as to prevent
any risk. Electrical installation of equipment shall be in compliance with these
installation instructions and with all National and Local Regulations for Electrical Safety.
To reduce the risk of fire, electrical shock and injury to persons, the following safety
instructions shall be used:
This pump is intended for indoor use with water only (max 25°C).
This pump is NOT SUBMERSIBLE.
Disconnect ALL power supplies before starting installation, connection or
maintenance work.
This pump is provided with a grounding conductor. To reduce the risk of electric
shock, be certain that it is connected only to a properly grounded, grounding type
receptacle.
All interconnecting tubes and cables should be confined within the air conditioning
unit, or enclosed in any way
During electrical installation, make sure this condensate pump is connected to a
circuit having switch with contact separation in all poles that provide full
disconnection from the power supply under over-voltage categories III
During electrical installation, a fuse non-time delay (rated 250V 1A), shall be fitted
into the line, supply side, see electrical installation section.
The power cord is not replaceable. If the power cord is damaged then the entire
pump must be replaced.
Children should be supervised to ensure that they are not left unattended in the area
where the pump is in use.
Children or persons with reduced physical, sensory or mental capabilities which limits
their ability to use the appliance should have a responsible person to instruct them in
its use.
Do not allow any chemicals to come into contact with this pump. Remove the pump
from the system before using cleaning fluid or any other chemicals. Flush the system
with clean water before re-connecting the pump.
All fittings on this pump are designed to be finger-tight. The use of tools to attach
pipework may result in damage to the pump.
In any installations where property damage and/or personal injury might result from an
inoperative or leaking pump, it is strongly recommended that the alarm relay should be
used to operate an alarm and/or switch off the air conditioning unit.
GB
2

Outlet
Breather support
Breather tube
Inlet
connector
Inlet
Fig.1.
Operation
The YUMA contains an internal sensor that will automatically start the pump when
condensate is detected and stop the pump when the condensate has been removed.
The YUMA is also fitted with a high water level alarm that will operate the alarm relay if
the water level rises to abnormal levels. The pump will continue to run until the minimum
water level is reached and the alarm will reset.
Installation
The YUMA pump can be installed at any angle between horizontal and vertical so long as
the breather tube inlet is above the condensate inlet (Fig. 3). The YUMA can also be tilted
sideways up to 30° from horizontal (Fig. 2).
The YUMA pump should be positioned in a suitable location within the equipment below
the level of the collection tray. The top of the breather tube should be positioned above
the highest part of the collection tray to avoid overflowing (Fig. 4). The YUMA pump,
condensate tubes and mains cable should be kept away from panels and surfaces and,
where possible, insulated with foam to minimise noise.
90
°
Fig.3.
ü
û
ü
30
°
30
°
Fig.2.
ü
ü
ü
Fig.4.
ü
Drain hose
Inlet connector
Foam insulation
GB
3

Fig.5.
Alarm Contacts
Volt Free Break On Fault connection
is rated 5 amps 1250VA. It may be
necessary to use a contactor if the air
handler supply is to be switched.
Cable Connections
Wire Colour
Connect
Symbol
1 GREEN/ YELLOW
EARTH
E
2 BLACK
LIVE
L
3 WHITE
NEUTRAL
N
4 VIOLET
Alarm contact
5 VIOLET
Alarm contact
E
L
N
POWER SUPPLY
CONTROL
CIRCUIT
1A
FUSE
1
2
3
4
5
Wiring Connections
Connect the ground, live and neutral wire from the supply cable of the YUMA pump to
the supply terminals (see Fig.6)
This product must be connected using a switch with contact separation in all poles that
provide full disconnection from the power supply under over-voltage categories III. A
fuse non time delay (rated 250V 1A), shall be fitted into the line, supply side (see Fig.5).
Testing
Before testing, ensure that the collection tray and drain hose is free of dirt and debris.
Pour clean tap water into the collection tray until the pump starts. Pump operation may
be noisy initially until any air has been purged from the system.
Continue to add water and the pump should switch to full power and the alarm contacts
should open. Do not continue to add water if it becomes visible in the breather tube.
Allow the YUMA to clear the water. The pump should switch off and the alarm relay
should reset.
GB
4

WARRANTY
This product is guaranteed for two years to be free from manufacturing defects or faulty
materials. If it should fail for either of these reasons within two years from the date of
manufacture it will be repaired or replaced free of charge, at the option of REFCO
Manufacturing Ltd.
REFCO Manufacturing Ltd. can accept no liability whatsoever for any loss or damage
arising from the use of this product, however caused. Before using this product the user
should satisfy himself that it is suitable for use in the intended application and for the
manner in which it is intended that it be used.
This product is subject to continuous development and improvement and REFCO
Manufacturing Ltd. Reserves the right to alter the specification or design without prior
notice.
Trouble Shooting
Pump does not run:
Check fuse and electrical supply
connections.
Check that water is reaching the pump
sensor.
Pump continues to run with no water:
The water sensor can become over
sensitive if contaminated by dirt, mould or
certain cleaning chemicals. If this occurs
the pump may continue to run with no
water. Disconnect the YUMA from the
mains supply and flush the sensor by
pouring clean tap water into the inlet for
around 30 seconds (Fig. 6). If the problem
persists, flush with methylated spirit and
then rinse with water.
Pump is noisy:
Check that the YUMA, mains cable and
outlet tube are not vibrating against the
sides of the equipment.
Fig.6.
Pump is pumping air:
Check that the YUMA is in the correct
orientation.
Check that the outlet tube is not syphoning.
In dirty environments an in-line filter is
recommended to avoid pump and sensor
damage.
GB
5