Setting (fig. 2)

1. Remove the cover from the device 

 by unscrewing the six screws 

2. Use the turnbuckle 

 to tighten the cable 

 until it is aligned with the index 

 opposite point 

3. Rotate the cam 

 to position it where required, based on the maximum allowable temperature difference in 

operation (fig. 3)

4. Use the rigging screw 

 to readjust the position of the index 

5. Arm the device by pressing the switch 

: you should hear a "click"

6. Actuate the device by pulling the cable 

7. Repeat steps 5 and 6 once more

8. Check the position of the index 

 and repeat steps 4 to 8 if required

9. Mount the cover onto the device 

 using the six screws 

 (tightening torque = 1.5±0.1 Nm / 

1.1±0.07 lb.ft

or move to the wiring stage

NOTE: The diagrams show a "right-anchored" device: reverse the diagrams for a "left-anchored" device.

NOTE: You can compensate for expansion/contraction of the cable by adjusting the configuration to take 

account of temperature variations:

• Fig.4a: anticipation of a fall in temperature,

• Fig.4b: anticipation of a rise in temperature.

RISK OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

• Switch off the power supply of the device

• Use appropriate personal protective equipment (PPE) and follow the relevant working instructions for 

electrical environments. See NFPA 70E.

• Always use an appropriate electrical measuring device to confirm that the entire installation is powered 

down.

Failure to follow these instructions will result in death or serious injury.

RISK OF UNINTENDED EQUIPMENT OPERATION

Check that the device, cable and accessories are securely mounted in place

Failure to follow these instructions will result in death or serious injury.

RISK OF FALL, COLLISION OR CRUSHING

• Do not pull on the cable while adjusting the cam

• Configure the device on the basis of the ambient temperature

Failure to follow these instructions can result in death, serious injury, or equipment damage.

DANGER DANGER DANGER WARNING

schneider.fm  Page 4  Friday, May 31, 2013  2:21 PM